14

Alarm Operation

Indications on the Display
If the defrost, or compressor key blinks, it means that the
corresponding function is delayed by a timing routine or
inhibited. Other two-character messages may appear on
the screen to indicate changes of state or alarm condi-
tions. Values shown in Table 1.

Viewing and Changing the Temperature Setpoint
The temperature setpoint is the comparison point for the
control temperature input. To change the set point value:

1. Press the Alarm key for more than 5 seconds until the

setpoint is displayed and blinking.

2. Press the Compressor key and Defrost keys to

raise/lower the value.

3. Press the Alarm key again to accept the new value.

Changing Other Setpoints
There are two levels of setpoints in the ESC3. The first
level does not require a password to change (unless the
buttons are locked out). The setpoints that can be
changed in this manner are identified in Table 1 (back
side) as a USER setpoint. All other setpoint do require a
password to change and are identified in Table 2 (back
side) as an OEM setpoint. To change USER-level set-
points:

1. Press the Alarm key and hold it until the letters PS are

displayed.

2. Use the Compressor and Defrost key to scroll through

the codes for the different set points (see Table 1 and
Table 2).

3. When the code is displayed for the setpoint you wish to

change, press the Alarm key. The value for that
setpoint will be displayed.

4. Press the Compressor or Defrost key to change the

value

5. Press the Alarm key to go back to the code.

At this point you must press the Alarm key to accept the
change or press the Compressor or Defrost key to scroll
to the next USER setpoint. To accept the changes, press
and hold the Alarm key until the display stops flashing. To
change OEM-level setpoints, the password must be
entered. To do this press and hold the Alarm key until the
letters PS are displayed. When PS is displayed release
the alarm key and 0 will be displayed. Press the
Compressor or Defrost keys to enter the password (22 is
the default) then press the Alarm key. PS will be dis-
played again. At this point, pressing the Compressor or
Defrost key will scroll through the legend for all setpoints.
To change the setpoints, use the identical procedure that
is used to change a USER setpoint.

Code

Meaning

E0

Air probe has failed

E1

Defrost termination or product probe has failed

LO

Low temperature alarm

HI

High temperature alarm

Ed

Defrost timeout has occurred
(did not terminate correctly)

dF

Case is in defrost (not an alarm)

Table 1

K1

J4

J6

J5

R1

K2

1

5

4

6

120V

ac

Neutral

Fan

Compressor

120V Hot

Defrost

Amb temp

Common

Def temp

ESC3 Case Controller

Alarm Key

Defrost Key

Compressor Key

Control Input

0.39 A, 120 Vac, 60 Hz

Common Input

11.2 A, 120 Vac, 60 Hz

Fan Output

1 FLA, 6 LRA, 120 Vac, 60 Hz

Compressor Output

1.5 HP @ 120 Vac

(K2)

(external relay #841-S-1A-D
by Song Chuan)

Defrost Output

10.0 A, 120 Vac, Resistive, 60 Hz

(P/N 850-3500 only)

CONTROL SETTINGS

ESC3 Controls