haier 0010518358 User Manual

Page 14

Advertising
background image

Disturbances in your electrical current can trip (Reset

button will pop out) the power supply cord. Press and

release RESET (listen for click; Reset button will latch and on

some devices, a green light will turn on) to resume operation.

Electrical overloading, overheating, cord pinching or aging

can trip (Reset button will pop out) the power supply cord.

After correcting the problem, press and release RESET (listen

for click; Reset button will latch and on some devices, a green

light will turn on) to resume operation.

NOTE: A damaged power supply cord must be replaced with a

new power supply cord obtained from the product manufacturer

and must not be repaired.

The air conditioner is not properly sized for your room.

Check the cooling capabilities of your room air conditioner.

Room air conditioners are not designed to cool multiple rooms.

The filter is dirty or obstructed by debris. Clean the filter.

There is excessive heat or moisture (open container

cooking, showers, etc.) in the room. Use a fan to exhaust

heat or moisture from the room. Try not to use heatproducing

appliances during the hottest part of the day.

The louvers are blocked. Install the air conditioner in a

location where the louvers are free from curtains, blinds,

furniture, etc.

The outside temperature is below 61°F (16°C). Do not try to

operate your air conditioner in the cooling mode when the out-

side temperature is below 61°F (16°C).

The temperature of the room you are trying to cool is

extremely hot. Allow extra time for the air conditioner to cool

off a very hot room.

Windows or doors to the outside are open. Close all

windows and doors.

The Temperature control is not at a cool enough setting.

Adjust the TEMP/TIME control to a cooler setting by

pressing the minus button to reduce the temperature. Set the

Fan Speed control to the highest setting.

The current air conditioner replaced an older model. The

use of more efficient components may cause the air conditioner

to run longer than an older model, but the total energy

consumption will be less. Newer air conditioners do not emit

the “blast” of cold air you may be accustomed to from older

air conditioners, but this is not an indication of lesser cooling

capacity or efficiency. Refer to the efficiency rating (EER) and

capacity rating (in Btu/h) marked on the air conditioner.

The air conditioner is in a heavily occupied room, or

heatproducing appliances are in use in the room. Use

exhaust vent fans while cooking or bathing and try not to use

heatproducing appliances during the hottest part of the day. A

higher capacity air conditioner may be required, depending on

the size of the room being cooled.

The air conditioner is not properly leveled. The air conditioner

should slope slightly downward toward the outside. Level the

air conditioner to provide a downward slope toward the

outside to ensure proper drainage. See the Installation

Instructions.

NOTE: Do not drill a hole into the bottom of the metal base

and condensate pan.

An extension cord is being used. Do not use an extension

cord with this or any other appliance.

You are trying to restart the air conditioner too soon after

turning off the air conditioner. Wait at least 3 minutes after

turning off the air conditioner before trying to restart the air

conditioner.

Air conditioner power supply cord trips (Reset button

pops out)

Air conditioner cycles on and off too much or does not

cool room in cooling mode

Air conditioner seems to run too much

Water drips from cabinet into your house

14

15

Advertising