Termination locations, Warning, A. vent termination minimum clearances – Hearth and Home Technologies 8000TV-OAK-IPI User Manual

Page 22

Advertising
background image

Heat & Glo • 8000TV-OAK, 8000TV-OAK-IPI, 8000TVLP-OAKIPI • 2058-900 Rev. N • 11/08

22

Figure 6.3 Leveled Termination Caps

A. Vent Termination Minimum Clearances

Roof Pitch

H (Min.) Ft.

Flat to 6/12...........................................................1.0*
Over 6/12 to 7/12 .................................................1.25*
Over 7/12 to 8/12 .................................................1.5*
Over 8/12 to 9/12 .................................................2.0*
Over 9/12 to 10/12 ...............................................2.5
Over 10/12 to 11/12 .............................................3.25
Over 11/12 to 12/12 .............................................4.0
Over 12/12 to 14/12 .............................................5.0
Over 14/12 to 16/12 .............................................6.0
Over 16/12 to 18/12 .............................................7.0
Over 18/12 to 20/12 .............................................7.5
Over 20/12 to 21/12 .............................................8.0

Figure 6.1 Minimum Height From Roof To Lowest Discharge
Opening

* 3 foot minimum in snow regions

6

6

Termination Locations

Fire Risk.

Maintain vent clearance to combustibles as
specifi ed.

DO NOT pack air space with insulation or other

materials.

Failure to keep insulation or other materials away
from vent pipe may cause overheating and fi re.

WARNING

B-VENT GAS, WOOD OR FUEL

OIL TERMINATION

A

GAS

TERMINATION

B

C

Wood & Fuel Oil

Termination

Comments

A

6 in.

20 in. min.

Horizontal distance between terminations

B

8 ft.

8 ft. min.

Distance to perpendicular wall

C

18 in.

18 in.

Vertical distance between terminations

Gas

Termination

B-VENT GAS, WOOD OR FUEL

OIL TERMINATION

8 FT.

(2.4 M)

(MINIMUM) TO

PERPENDICULAR

WALL

(GAS ONLY)

WOOD OR

GAS TERMINATION

20 IN. MIN. *

(508 MM)

* IF USING DECORATIVE CAP COVER(S), THIS DISTANCE MAY

NEED TO BE INCREASED. REFER TO THE INSTALLATION
INSTRUCTIONS SUPPLIED WITH THE DECORATIVE CAP COVER.

Figure 6.2 Staggered Termination Caps

VERTICAL

WALL

LISTED B-VENT

TERMINATION

CAP

12

X

ROOF PITCH

IS X/ 12

LOWEST

DISCHARGE

OPENING

H (MIN.) - MINIMUM HEIGHT FROM ROOF
TO LOWEST DISCHARGE OPENING

8 FEET