Honeywell 800-04433V1 User Manual

Page 9

Advertising
background image

iPGSM-COM Commercial Fire Communicator – Installation and Setup Guide

– 7 –

STEP 6 – Configure the Fire Panel

1. Ensure the Telco Fault on the panel is enabled. Then choose a setting that is no higher than 90

seconds (or as close to that) as the panel allows.

2. Ensure no more than 1 pause character (usually a comma) is programmed into the dialing string

(usually 2 seconds). Note, this is necessary since the Dialer Capture Module waits only 3 seconds

after the phone number is dialed. Having more than 3 seconds of pause time will cause it to think
the phone number is complete and cause it to generate the high-low tones at an incorrect moment.

STEP 7 – Test the System

1. Close the Wall Outlet Box, then close and lock the cabinet cover.

2. Refer to the fire panel's installation/operation guide the testing procedure.
3. (Notify the monitoring station that a test will be conducted.) Test the system to ensure it is

operating.

iPGSM-COM Trouble Detection Information

Telco 1 is used for the Fire Panel to output contact ID messages to the iPGSM-COM, and Telco 2 is used by
the iPGSM-COM to report faults to the Fire Panel. If Telco 1 is not operational, the Fire Panel will use

Telco 2 to report events if there are no faults in the iGSM Communications module.

Fault Condition

Indication to Fire Panel

PowerBoost1 fault

Telco 2 is cut.

iGSM Communications Module fault

 Failure of one of the two

communications paths.

Telco 2 is cut.

 Failure of both communications

paths.

Telco 1 and 2 are cut.

Dialer Capture Module buffer is full.

Hang up. (Panel will retry, giving the buffer a chance to empty.)









Advertising