Specifications, Installation instructions – gohastings.com EC-40 User Manual

Page 3

Advertising
background image

SPECIFICATIONS

Model

(EC)

40 80 120

160

220

300

400 500

600

750

Dry

Weight

110 176 225

271

310

373

634 726

845

1067

Operation Weight**

335

560

650

825

880

1135

1680

1930

2085

2635

Pump Cap/GPH req.*

270

360

540

720

720

810

540+

630+

630+

630+

Cap/GPH @ Lift*

387

1135

1135

1135

1135

1100

1080

1080

1060

1060

Pump Lift/ft.

3

4

4

4

4

5

6

6

7

7

* These figures do not include the 3 to 6 percent bleed-off rate required to reduce scaling for standard unit.
**Unit in operation, media fully saturated.
+ Per pump
EC = Evaporative cooler


WATER CONNECTIONS ALL UNITS

1-1/2 FPT Overflow

¾ FPT Drain

½ MPT Bleed-off

½ FPT Float Valve

ELECTRICAL SPECIFICATION

Model

(EC)

40

80 120 160 220 300 400 500 600 750

Pump Motor Model

CP 1000

5 MSP

(2) 5 MSP

HP

1/50

1/6

1/6

Amperage

1.1 A

5.0 A

5.0 A

Voltage 115

V

EC = Evaporative Cooler

APPROXIMATE BLEED-OFF FLOW RATE

Model

EC-40 -80

EC-120 -160

EC-220 -300

EC-400 -750

Per Minute

½ to 1 qt.

1 to 2 qt.

2 to 3 qt.

2 (2-3 qt.)

CONSTRUCTION AND MEDIA SPECIFICATION

Celdek Glasdek

Maximum Water Temperature

130ºF

165ºF

Maximum Air Temperature

300ºF

300ºF

pH Range

6-9

6-9

Cabinet

Aluminized Steel and Painted

Evaporator Reservoir

Stainless Steel and Painted

INSTALLATION INSTRUCTIONS



1. When installing the evaporative cooler, special consideration should be given to the physical positioning of

the unit, electrical power supply, the proper water supply, and the structural members to support the
cooler at the operating weights. It is recommended that supports be placed within every four feet to
distribute the weight evenly. Be sure the supports are level.

2. After the unit is properly located, electrical connection may be made. If the Evaporative Cooler has been

purchased separately, wiring from a 115 volt supply may be connected to the junction box supplied with
the unit. Refer to the wiring schematic supplied in owner’s packet or, pages 4 and 5 of typical wiring
schematics, and to drawings for standard unit, units with automatic drain kit, or units with automatic drain
kit and freeze protection.
When the evaporator cooler is purchased with a system exhaust blower and filter, most connections
may have been made already. Refer to schematic with owner’s packets for any additional wiring to be
done.

- 3 -