Vertical Condenser

Vertical airflow units should be located no closer than the width

of the unit from a wall or other obstruction. If two or more units

are to be positioned in the same area, a similar distance should

be maintained between adjacent units. Sufficient free area

should be left around and below unit to avoid air restriction

to coil.

Leg Assembly for Vertical Airflow Installation

(Models 008-016; 1-3)

Assemble the unit’s two legs (Figure 3, item ) using three

1/4 - 0 x 3/4” long bolts per leg. Captive nuts are provided

on unit for this assembly.
Four gussets (Figure 3, item 3) are provided for

leg support.
Assemble the gusset in each corner with 1/4 - 0 x 3/4” long

bolts and 1/4” nuts.
Discard the four mounting angles (Figure 5, item 1).

Leg Assembly for Vertical Airflow Installation

(Models 024-133; 5-26)

1.

.

3.

4.

Remove fasteners securing condenser to skid.
Remove leg extensions (Figure 4, item 1) by removing four

5/16” x 3-1/” bolts.
Install as shown in dotted lines with same four bolts.
Install mounting angle (item ) as shown (dotted lines) with

four 1/4 - 0 x 3/4” bolts provided.
Condenser can be hoisted by attaching hooks into 1-1/”

holes in leg assemblies.

Horizontal Condenser

Horizontal airflow units should be installed with the coil (inlet

air side) facing the prevailing winds. Where strong winds

are common, it is recommended that a wind deflector (not

supplied) be used to discharge the air vertically from the unit,

to prevent capacity loss during varying wind conditions. The

wind deflector should be installed on the fan side of the unit.

If horizontal airflow units are installed with the air inlet facing

a wall, a distance of at least 48 inches should be maintained

between unit and wall. If it is necessary to have the unit

positioned so the air discharge is toward a wall, it should be

spaced at a distance no less than three times the coil face

height from the wall.

Leg Assembly for Horizontal Airflow Installation

(Models 008-016; 1-3)

Attach four mounting angles (Figure 5, item 1) to the

unit, using two 1/4 - 0 x 3/4” long bolts and 1/4” nuts per

mounting angle.
Discard the two legs, (Figure 3, item ) and four gussets

(Figure 3, item 3).

1.
.

3.
4.

5.

1.

.

4

Part # 500018

Installation and Operations Manual

Figure 5. Leg assembly (horizontal airflow, models 008-016 ; 1-3)

Figure 4. Leg assembly (vertical airflow, models 024-133; 5-26)

Figure 3. Leg assembly (vertical airflow, models 008-016; 1-3)