Performance data, Model elc/efc electric defrost | 60 hz, Model elc/efc electric defrost | 50 hz – Heatcraft Refrigeration Products Air Defrost RLC User Manual

Page 6

Advertising
background image

6

Model ELC/EFC

Electric Defrost | 60 Hz

Model

Capacity

Fan Data

10°F TD

-20°F SST

6°C TD

-29°C SST

No.

CFM

m

3

H

BTUH

Watts

6 F

ins P

er I

nch

ELC035

3,500

1,025

1

700

1,189

ELC040

4,000

1,170

1

700

1,189

ELC047

4,700

1,380

1

650

1,104

ELC065

6,500

1,900

2

1,400

2,379

ELC075

7,500

2,200

2

1,300

2,209

ELC090

9,000

2,640

2

1,300

2,209

ELC120

12,000

3,520

3

2,100

3,568

ELC140

14,000

4,100

3

1,950

3,313

ELC160

16,000

4,690

4

2,600

4,418

ELC180

18,000

5,280

4

2,600

4,418

ELC200

20,000

5,860

5

3,250

5,522

ELC240

24,000

7,030

6

3,900

6,627

ELC280

28,000

8,200

6

3,900

6,627

4 F

ins P

er I

nch

EFC041

4,100

1,200

1

690

1,172

EFC068

6,800

2,000

2

1,380

2,345

EFC080

8,000

2,340

2

1,380

2,345

EFC102

10,200

2,990

3

2,170

3,687

EFC136

13,600

3,990

4

2,760

4,690

EFC170

17,000

4,980

5

3,450

5,862

EFC204

20,400

5,980

6

4,140

7,035

EFC235

23,500

6,880

6

4,140

7,035

Performance Data

Model ELC/EFC

Electric Defrost | 50 Hz

Model

Capacity

Fan Data

10°F TD

-20°F SST

6°C TD

-29°C SST

No.

CFM

m

3

H

BTUH

Watts

6 F

ins P

er I

nch

ELC035

3,325

974

1

630

1,070

ELC040

3,800

1,113

1

630

1,070

ELC047

4,465

1,308

1

586

995

ELC065

6,175

1,809

2

1,260

2,142

ELC075

7,125

2,087

2

1,170

1,989

ELC090

8,550

2,504

2

1,170

1,989

ELC120

11,400

3,339

3

1,891

3,213

ELC140

13,300

3,896

3

1,756

2,984

ELC160

15,200

4,452

4

2,341

3,978

ELC180

17,100

5,009

4

2,341

3,978

ELC200

19,000

5,565

5

2,927

4,973

ELC240

22,800

6,678

6

3,512

5,967

ELC280

26,600

7,791

6

3,512

5,967

4 F

ins P

er I

nch

EFC041

3,895

1,141

1

621

1,056

EFC068

6,460

1,892

2

1,243

2,111

EFC080

7,600

2,226

2

1,243

2,111

EFC102

9,690

2,838

3

1,954

3,320

EFC136

12,920

3,784

4

2,485

4,223

EFC170

16,150

4,731

5

3,107

5,279

EFC204

19,380

5,677

6

3,728

6,334

EFC235

22,325

6,539

6

3,728

6,334

For EC motors, use 60 Hz capacity and airflow values (Units with EC motors

operating at 50 Hz will not see a reduction in performance due to the electronic

control of the motor)

Capacity Correction Factors For

Electric and Hot Gas Defrost Units

Saturated Suction

Temperature °F

+20

-10

-20

-30

Saturated Suction

Temperature °C

-7

-23

-29

-34

Multiply Capacity

By

1.15 1.04 1.00 0.90

Advertising