22

Figure 26. 12" x 12" Hole and Vent Pipe

Figure 27. Heat Shield, Interior & Exterior Firestops

VENT PIPE

1" (25.4 mm)

12"

(305mm)

12"

(305mm)

TRIM HEAT
SHIELD IF TOO
LONG, ADD TO
SHIELD IF TOO
SHORT

EXTERIOR
FIRESTOP

INTERIOR

FIRESTOP

HEAT SHIELD

NOTE: There must be NO INSULATION or other
combustibles inside the framed firestop opening.

For Vertical Runs - One ceiling firestop is REQUIRED at
the hole in each ceiling through which the vent passes.

To install firestops for vertical runs that pass through ceilings:

• Position a plumb bob directly over the center of the verti-

cal vent component.

• Mark the ceiling to establish the centerpoint of the vent.

• Drill a hole or drive a nail through this centerpoint.

• Check the floor above for any obstructions, such as wir-

ing or plumbing runs.

• Reposition the fireplace and vent system, if necessary,

to accommodate the ceiling joists and/or obstructions.

• Cut an 11-inch X 11-inch (280mm X 280mm) hole through

the ceiling, using the centerpoint previously marked.

• Frame the hole with framing lumber the same size as the

ceiling joists.

Figure 28. 11" x 11" Hole & New Framing Members

CEILING

NEW
FRAMING
MEMBERS

EXISTING CEILING
JOISTS

CHIMNEY
HOLE

11" (280 mm)

11" (280mm)

• Position the firestops on both sides of the hole previ-

ously cut and secure the firestops with nails or screws.

• The heat shields of the firestops MUST BE placed to-

wards the top of the hole.

• Continue the vent run through the firestops.

4. Install Firestops

For Horizontal Runs - Firestops are REQUIRED on both
sides of a combustible wall through which the vent passes.

NOTE: Model DVK-01TRD does not need an exterior
firestop on an exterior combustible wall.

To install firestops for horizontal runs that pass through
either interior or exterior walls:

• Cut a 12” x 12” (305mm x 305mm) hole through the wall.

NOTE: The center of the hole is one (1) inch (25.4mm)
above the center of the horizontal vent pipe.

WALL BRACKET

WALL STUD

1 INCH MIN.

(25.4mm)

8 FT. (2.4m)

FLUE

OUTLET

Figure 25. Installing Support Brackets