Operation – Heatiator Heatilator BH60 User Manual

Page 24

Advertising
background image

24

Operation

Control Board Operation

Aquastat Sensor - This sensor is located in the aqua-

stat well on the top of the water jacket. This sensor

along with the outdoor air sensor is what the control

board uses to regulate the feed rate based on these two

observed conditions. (Boiler Temp. & Outdoor Air

Temperature)

Outdoor Air Temp. Sensor (OAT) - This sensor is

located outside the building (on the north side of the

house and out of direct sunlight). The Outdoor Air

Sensor is used to perform hot water reset based on out-

door air temperatures.

When the OAT sensor is installed, at 20° F. or below

(outside temperature), the boiler will operate at the

temperature set on the MAX. TEMP. knob. The boiler

water temperature will decrease by 1 degree F. for

every 1 degree F. in temperature rise (above 20°) of

the outdoor air.

NOTE: Pellet Boiler Outdoor Air Reset Operation

Graph located on page 23.

WATER TEMPERATURE

MAX. TEMP.

MIN. TEMP.

Setting The Boiler Temperature

Without the Outdoor Air Temperature Sensor

Installed

To set the maximum boiler water temperature, sim-

ply turn the Max. Temp. water temperature dial to the

desired setting. The control and the boiler will then

perform to achieve and maintain the set temperature.

The Min. Temp. Knob is the boiler water tempera-

ture minimum, or the lowest temperature the water

will go before the unit re-starts. Turning the knob fully

counter-clockwise is the “OFF” position, while turn-

ing the knob clockwise, past the 140 degree marking,

is the “ON” position..

With The Outdoor Air Temp - Sensor Installed

Maximum boiler temp setting is as described above.

The MIN. TEMP. knob in addition to being the

mode setting (on or off) now also has the function of

setting the minimum boiler water temperature. This

would be the lowest boiler water temperature that you

want to have based on the following factors.

1.) Outdoor Air Temperature (OAT)

2.) Domestic Hot Water Use

a.) Hot Water Coil Option

b.) Indirect Hot Water Storage

3.) Overall Volume of the Heating System

The boiler is designed to withstand lower return water

temperatures however, extended return temperatures below

140 degrees F can cause condensation in the secondary

ash chamber area and also in the venting system, which

could cause damage in these areas.

NOTE:

If the system is run at the lower temperature settings, con-

ditions of the firebox, boiler tubes, secondary ash chamber

and venting should be monitored closely. If conditions show

excess condensation, the boiler water minimum tempera-

ture will need to be increased until condensation does not

occur. You should also consider some form of tempering of

the return water system. Discuss this with your plumber.

Advertising