VENTING WITH ONE (1) 90° ELBOW

V (FT.)

H (FT.)

1' MIN. (305mm)

5' MAX. (1.52m)

2' MIN. (610mm)

10' MAX. (3.1m)

3' MIN. (914mm)

15' MAX. (4.65m)

4' MIN. (1.22m)

20' MAX. (6.2m)

V+H= 40’ MAX. (12.4MM) 20' MAX. (6.2m)

Figure 7. Venting with One 90° Elbow

NOTE: IF A 90

o

ELBOW IS FIRST AT-

TACHED TO THE UNIT, THE MAXIMUM

HORIZONTAL RUN IS 3-FEET (914mm).

NOTE: For corner installations: A 6-inch (152mm) MINIMUM length of straight pipe must be attached to the

fireplace before 90

o

elbow. This will allow the vent pipe to clear the top standoffs.