Chapter 12 Error Code List and Special Internal Outputs

12-6

No.

Name

Meaning

Description

Setting

condition

Resetting

condition

R7D7 Undefined

Do not use.

R7D8 Undefined

Do not use.

R7D9

Battery error

0: Normal
1: Abnormal

Indicates whether battery voltage is
low

Set by the
system

Cleared by
the system *2

R7DA

*1

Instantaneous power
failure detection

0: Not detected
1: Instantaneous power failure detected.

Set by the
system

R7DB

Self-diagnostic error

0: Normal
1: Error

Indicates whether there is a self-
diagnostic error (Detailed information
output to WRF000)

Set by the
system

R7DC

Output mode

0: Stops output
1: Continues output

Operation mode at CPU stop for PWM
output, pulse output and counter
coincidence output.

Set by user

Cleared by
user, Cleared
when
retentive area
is cleared, or
the CPU is
initialized.

R7DD Undefined

Do not use.

R7DE Undefined

Do not use.

R7DF Undefined

Do not use.

R7E0 Key switch location

(STOP)

0: at RUN position
1: at STOP position

Set by the
system

Cleared by
the system

R7E1 Undefined

Do not use.

R7E2 Key switch location

(RUN)

0: at STOP position
1: at RUN position

R7E3 1

st

scan ON after

RUN

1: 1

st

scan after RUN

ON only at the 1

st

scan.

Cleared by
the system

R7E4

Always ON

1: Always

Always ON regardless of CPU status

Cannot be
cleared.

R7E5

0.02 second clock

0: 0.01 seconds
1: 0.01 seconds

R7E6

0.1 second clock

0: 0.05 seconds
1: 0.05 seconds

R7E7

1.0 second clock

0: 0.5 seconds
1: 0.5 seconds

R7E8

CPU Occupation

0: Unoccupied
1: Occupied

Indicates CPU occupation status from
the peripheral unit

R7E9

RUN prohibited

0: Operation allowed
1: Operation prohibited

Indicates whether it is operation
prohibited status

R7EA

Executing a online
change in RUN

1: Being executed

Indicates whether operation is
temporarily stopped (output hold) due
to online change in RUN

Set by the
system

Cleared by
the system

*1:

Supported by software version 1.11 (WRF051=H0111) or newer.

*2:

The battery error (R7D9) will turn off when the error cause is eliminated by replacing the battery, etc.