(Continued from previous page)

Display

Function

Standard

Setting

Set

Value

A94

PID feedback signal location / I gain setting
0-PID control not active
1-Terminal OI / 1

2-Terminal O / 1

3-Terminal OI / 10

4-Terminal O / 10

0

A95

PID control set value setting
0-Via

A96

1-Via

A 9

0

A96

PID control internal set value (in %)

0

A97

Autotuning mode:

0-Autotuning off

1-Autotuning on 2-Autotuning / static

0

A98

Motor data: 0- Standard Hitachi 1-Hitachi-
special motors 2-Read in motor data

0

A99

Power supply phase breakdown will cause
trip

E24

: 0-Yes 1-No

0

Display

Function

Standard

Setting

Set

Value

C

0

Function of input terminal 1
0-REV (Reverse run) 1-CF1 (Multispeed 1)
2-CF2 3-CF3 5-JG (Jogging)
6-DB (External DC braking)

7-STN (factory setting) 8-SET (Use 2. setting)

9-CH1 (2. stage acceleration/deceleration)
11-FRS (free run mode)

12-EXT (external trip) 13-USP (USP function)

14-CS (Motor free run) 15-SFT (Software
lock) 16-AT (Use analog input OI)

18-RS (Reset) 27-UP (Remote control accele-

ration) 28-DWN (Remote control deceleration)

18

C

1

Function of input terminal 2 (See

C

0

)

16

C

2

Function of input terminal 3 (See

C

0

)

5

C

3

Function of input terminal 4 (See

C

0

)

11

C

4

Function of input terminal 5 (See

C

0

)

9

C

5

Function of input terminal 6 (See

C

0

)

2

C

6

Function of input terminal 7 (See

C

0

)

1

C

7

Function of input terminal 8 (See

C

0

)

0

C10

Function of output terminal 11:
0-FA1 (frequency arrival)
1-RUN signal (Motor running)
2-OTQ (torque alarm; only usable when SLV
mode is active)

0

C11

Function of output terminal 12 (See

C10

)

1

C20

Digital input type 1-4: Normally open (no)
or Normally closed (nc)

Input1 Input2 Input3 Input 4

00

no

no

no

no

01

nc

no

no

no

02

no

nc

no

no

03

nc

nc

no

no

04

no

no

nc

no

05

nc

no

nc

no

06

no

nc

nc

no

07

nc

nc

nc

no

08

no

no

no

nc

09

nc

no

no

nc

0A

no

nc

no

nc

0B

nc

nc

no

nc

0C

no

no

nc

nc

0D

nc

no

nc

nc

0E

no

nc

nc

nc

0F

nc

nc

nc

nc

08

C21

Digital output type 11, 12 and alarm output:
Normally open (no) or Normally closed (nc)

07 06 05 04 03 02 01 00

Output 11 nc no nc no nc no nc no
Output 12 nc nc no no nc nc no no
Alarm

nc nc nc nc no no no no

04

Display

Function

Standard

Setting

Set

Value

A

0

Characteristic V/F curve setting
0-constant torque
1-M ~ n

1,5

2-M ~ n

1,7

3-M ~ n

2

4-SLV 5-SLV

+

feedback

0

A

1

Motor capacity setting

Cf. nameplate

A

2

Motor poles: 2, 4, 6, 8

4

A

3

ASR constant

2

A

4

Start frequency setting

0.5

A

5

Maximum operating frequency setting

0

A

6

Minimum operating frequency setting

0

A

7

A

8

A

9

Jump frequency setting

0

A10

Carrier frequency (in kHz)

Depends on

model

A11

Time constant of the filter for analog inputs

8

A12
A13
A14

Multispeed frequency setting

All are 0

A23

Level of electronic thermal setting (in % of
the inverter rated current)

100

A24

Selection of electronic thermal characteristic
00-Constant torque 01-Reduced torque
02-Freely configurable (using remote)

0

A25

Motor pole count for rpm monitor via

d 1

4

A26

External frequency setting start point

0

A27

External frequency setting end point

0

A34

Selection of restart mode 00-Alarm

01-Motor speed match restart /decel to stop

02-Motor speed match restart
03-Start frequency restart after waiting time

0

A38

Rate of use (in %) of the regenerative braking
resistor (00= braking resistor not active)

0

A39

Arrival frequency setting for acceleration (Hz)

0

A40

Arrival frequency setting for decelerat. (Hz)

0

A44

Function of FM terminal
00-Frequency 01-Current
02-Torque 03-Frequency (digital)

0

A47

Factor for

d 3

monitor

1

A48

Frequency set value range
0-Range 0-5V 1-Range 0-10V

1

A49

FA1 signal characteristic: output signal ...
0-on arrival of set value
1-above frequencies set via

A39

/

A40

2-on crossing frequencies set via

A39

/

A40

0

A54

Selection of operation when FRS signal is
cancelled:

00-Restart at motor speed
01-Restart at 0 Hz

01

A58

Step count on RV start (0= RV not active)

6

A59

Operating mode:
0-Normal mode 1-Energy saving mode
2-Shortest possible accel./decel.times

0

A61

Jog frequency setting

1.0

A62

Base frequency setting

50

A63

Maximum frequency setting

50

A64

Selection of largest settable frequency
(120Hz, 400Hz)

120

A80

Frequency command adjustment (terminal O)

A81

Frequency command adjustment (terminal OI)

Depends on

model

A86

RS terminal reset signal:
0-Rising edge 1-Falling edge

0

A90

P (proportional) gain setting

1.0

A91

I (integral) gain setting

1.0

A92

D (differential) gain setting

1.0

(Table to be continued on next page)

Wiring example: power terminals

Wiring example: control terminals

R

a

d

io

n

o

is

e

filte

r

Power source

External braking
resistor

6

7

8