Instructions to installation – haier AD122XLERA User Manual

Page 22

Advertising
background image

The connection of indoor unit pipes must use double spanners.
The installing torque shall be as given in the following table.

Double-spanner
operation

Pipe expansion dimensions as follows:

20

Pipe expander

A

Piping Connection

Flare connection

Gas pipe

3-way valve

Indoor
Unit

Outdoor
unit

Liquid
pipe

2-way valve

Flare connection

AD092XLERA
AD122XLERA

AD142XLERA
AD182XLERA

Flare connection

Gas pipe

3-way valve

Indoor
Unit

Outdoor
unit

Liquid
pipe

2-way valve

Flare connection

A

To outdoor unit

To gas pipe

A

(adaptor, from 9.52 to 12.7)

6.35 mm (1/4") 0.8 ~ 1.5

9.52 mm (3/8") 1.0 ~ 1.8

12.7 mm (1/2") 1.2 ~ 2.0

Pipe diameter

ÿ

Size A (mm)

Connecting pipe

O.D.(mm)

я6.35

я9.52

я12.70

Installing torque

(N-m)

11.8 (1.2kgf-m)

24.5 (2.5kgf-m)

49.0 (5.0 kgf-m)

Increased installing

torque (N-m)

13.7 (1.4 kgf-m)

29.4 (3.0 kgf-m)

53.9 (5.5 kgf-m)

Instructions to installation

Slope Damage Bur Partial Overlong

Correct

Incorrect