B. low temperature alarm (e2) – Hoshizaki HUR40A(-D) User Manual
Page 36
                                    Advertising
                                    
                                        
                                    
                                
                                 
36
b. Low Temperature Alarm (E2)
If the cabinet temperature drops below the setpoint temperature by 9°F (5°C) or more for 
more than y minutes, "E2" is displayed. The default value of y is "1" (1 hour). The value 
of y can be changed under F4 on the Settings and Diagnostics Menu. (0=No delay; 1=1 
hour)
Note:
• The low temperature alarm timer starts once the cabinet temperature drops 9°F
(5°C) below the setpoint temperature.
• The low temperature alarm feature operates even during defrost.
Reset Options
The alarm will automatically reset once the cabinet temperature reaches the upper setpoint 
temperature differential.
Possible Causes
•	Ambient	temperature	is	low.
•	Trouble	with	the	cabinet	thermistor	(black).