Freezers – continuous operating mode – Hoshizaki HUR40A(-D) User Manual
Page 15
 
15
2. Freezers – Continuous Operating Mode
a) Sequence of Operation
Note:
1) Cut-on, cut-off, and cabinet temperature are read by the same sensor, called the
"cabinet thermistor."
2) The defrost thermistor reads the evaporator temperature.
3) There is a five second evaporator fan startup delay when the compressor and 
fan would otherwise start together.
Five minutes after 
defrost heater off
1. Compressor on
2. Condenser fan on
Five minutes after 
compressor start-up
1. Evaporator fan(s) on
Eight minutes after evaporator 
fan start-up "dF" no longer 
displayed, cabinet temperature 
displayed
Board Self Check
1. Frame heater(s) on
2. Evaporator fan(s) on
POWER ON
2 minute delay
1. Compressor start-up
2. Condenser fan start-up
Cycle Off (Cut-out 
temperature reached) 
[Minimum 2 minutes]
1. Compressor off
2. Condenser fan off
Continue as 
normal cycling
Cycle On (Cut-on 
temperature reached) 
[Minimum 2 minutes]
1. Compressor start-up
2. Condenser fan start-up
Defrost end
Defrost thermistor 
reaches defrost 
termination 
temperature, or defrost 
timer reaches 1 hour
Defrost heater off
Defrost Start
Preprogrammed time interval
1. Compressor off
2. Evaporator fan(s) off
3. Condenser fan off
4. Defrost heater on
5. "dF" displayed