Heat & Glo • SOHO-N-AUB • 2197-980 Rev. G • 2/13

22

D. Mantel and Wall Projections

WARNING! Risk of Fire! Comply with all minimum clear-

ances as specified. Framing or finishing material closer than

the minimums listed must be constructed entirely of non-

combustible materials (i.e., steel studs, concrete board, etc).

Combustible Mantels

No mantels are allowed when using Studio-CE fronts.

Figure 5.3 Minimum vertical and maximum horizontal

dimensions of combustibles above appliance

when using the DF-SOHOCE-BK dress guard.

127

178

102

OPENING OF FIREPLACE

76

127

203

305

51

229

254

279

152

26

407

152

178

203

229

254

279

305

330

356

381

Note: All dimensions are shown in millimeters