Manning AirAlert-96d Gas Monitor

19073 AIRALERT96D 05/2006 Prelim REVC Copyright © 2006 Honeywell Analytics. All Rights Reserved.

23

10

Relay Module

(optional) continued

Wiring Details

Power Supply Cable

•

14 AWG stranded cable or larger (see your network
diagram provided by Honeywell Analytics sales
department).

Communication Cable

•

24 AWG twisted pair (Belden # 9841 or equivalent).

Figure 11. Relay Module PCB

Power

Tx Modbus

Normally
open

Normally
closed

3+5
4+6

1+3
2+4

6

4

2

5

3

1

RC

R

EOL1

Relay Outputs (J1-J8)
5A, 30 Vdc or 120 Vac (resistive load)

V+

V-

SHLD

A

B

J10

J10

J8

J7

J2

J1

From “B” terminal of controller
to “B” terminal of next device

From “A” terminal of controller
to “A” terminal of next device

From +24VDC terminal

of power supply

From Ground terminal

of power supply

NO

NC

NO

NC

Relay 2

NO

NC

Relay 3

Relay 1

NO

NC

Relay 4

NO

NC

NO

NC

Relay 6

NO

NC

Relay 7

Relay 5

NO

NC

Relay 8

End of Line Resistor
On the last device of the
communication network,
a jumper must be
installed as shown.

Power and TX
status LEDs

1
2
3
4

off

DIP switches