B. house style shroud – Hearth and Home Technologies BIR50-B User Manual

Page 34

Advertising
background image

34

B. House Style Shroud

• Field-fabricated spacing clips (1/2 in./13 mm tall, 24

ga/.024 in. galvanized steel) must be used to support the

chase top flashing or chase pan, in order to provide air

flow.

• 14 in. (345 mm) DuraChimney II pipe must extend at least

6 in. (152 mm) above the chase pan/flashing.

• A DuraChimney II cap must be used inside the shroud.

• The shroud must not be in direct contact with any of the

DuraChimney II components (other than the chase top

flashing).

The house-style shroud is roughly square or rectangu-

lar with a closed top and exhaust openings on four sides

(Figure 10.2). Table 10.1 lists the minimum shroud d9imen-

sions, the minimum open area per side, and the minimum

total open area for the shroud.

• All open areas of the shroud must be covered with 1/2

in. (13 mm) stainless or galvanized steel mesh screen to

prevent debris from entering the shroud.

• Shrouds must follow the dimensional requirements

specified in Tables 10.1, 10.2 or 10.3, depending on the

syle of shroud used. The three basic shroud styles are 1)

House, 2) Arch or Mailbox, and 3) Pyramid. Most factory-

fabricated shrouds will fall under one of these basic style

categories.

H

W

L

Shaded area represents screened open area. Actual

shape of shroud may vary as long as minimum dimen-

sions and minimum open area requirements are met.

H: Minimum height of shroud

L: Minimum length of shroud

W: Minimum width of shroud

Figure 10.2 House-Style Shroud Minmum Dimensions

House Style Shroud Minimum Dimensions

Chimney

Diameter

Chimney Area Min Height H Min Length L Min Width W

Min Open Area

per side

Min Total Open

Area

in

mm

in

mm

in

mm

in

mm

in

mm

sq in

sq in

14

355.6

154

3911.6

24

609.6

32

812.8

32

812.8

260

1040

Table 10.1

Heatilator • Birmingham BIR50-B • 4059-682D • 9/12