Warning – Heat & Glo Fireplace EXCLAIM-42T-C User Manual

Page 30

Advertising
background image

Heat & Glo • EXCLAIM-42C • 4013-094 Rev I • 10/06

30

B. Finishing Material

• Combustible

Material

Material which is made of or surfaced with wood,
compressed paper, plant

¿ bers, plastics, or any material

capable of igniting and burning, whether

À ame proofed or

not, plastered or not plastered.

• Non-Combustible

Material

Material which will not ignite and burn. Such materials are
those consisting entirely of steel, iron, brick, tile, concrete,
slate, glass or plasters, or any combination thereof.

Materials that are reported as passing ASTM E 136,
Standard Test Method for Behavior of Materials in a
Vertical Tube Furnace at 750° C
, shall be considered
non-combustible materials.

• Non-Combustible Sealant Material

Sealants which will not ignite and burn: Rutland, Inc.
Fireplace Mortar #63, Rutland 76R, Nuflex 304, GE
RTV106 or GE RTV116 (or equivalent).

After completing the framing and applying the facing material
(drywall) over the framing, a bead of non-combustible seal-
ant must be used to close off any gaps at the top and sides
between the

¿ replace and facing to prevent cold air leaks.

Large gaps can be bridged with

¿ berglass rope gasket.

Only non-combustible materials may be used to cover the
metal

¿ replace front.

E. Glass Doors

This

¿ replace has been tested and listed for use with doors

as speci

¿ ed in Section 12.B. Fireplace Components. Please

refer to the manual packed with each set of doors for instal-
lation instructions.

23-3/4 in.

(603 mm)

50°

42 in.

(1067 mm)

51-1/2 in.

(1308 mm)

39°

4 in.

(102 mm)

BRICK

FRONT

FLUSH FRONT

24 in.

(610 mm)

19-3/4 in.

(502 mm)

24 in.

(610 mm)

Figure 8.6

Sidewalls/Surrounds

Fire Risk

Do NOT obstruct air inlets.
Do NOT modify air inlets.
• Modifying or covering air inlets could cause

temperature rise and

¿ re hazard.

Finishing materials must not interfere with:
• Air

inlets

• Access for service

WARNING

C. Mantel

A combustible mantel may be positioned no lower than
12 in. (305 mm) above the top of the

¿ replace opening. The

combustible mantel may have a maximum depth of 12 in.
(305 mm). Combustible trim pieces that project no more
than 1-1/2 in.(38 mm) from the face of the

¿ replace can

be placed no closer than 6 in. (152 mm) from the top of the
¿ replace opening. See Figure 8.5. Combustible trim must
not cover the metal surfaces of the

¿ replace. This mantel

clearance is in accordance with Section 7-3.3.3 of ANSI/
NFPA211
.

D. Sidewalls/Surrounds

Adjacent combustible side walls must be located a minimum
of 24 in. (610 mm) from the

¿ replace opening. If you are us-

ing a decorative surround constructed of combustible ma-
terial, it must be located within the shaded area de

¿ ned in

Figure 8.6. Short stub walls are also acceptable if they are
contained within the shaded area.

12 in. MIN.

12 in.

71-3/4 in.

Effective

Height

Gas Knockout

Figure 8.5

Mantel Speci

¿ cations

Fire Risk
• Maintain

clearances.

• Use only non-combustible material below

standoffs, material such as cement board is
acceptable.

WARNING

• Framing

or

¿ nishing material used on the front of, or

in front of, the appliance closer than the minimums
listed, must be constructed entirely of noncombustible
materials (i.e., steel studs, concrete board, etc.).

Fire Risk

Finish all edges and fronts to clearances and
speci

¿ cations.

WARNING

• Metal fireplace front may be covered with non-

combustible material only.

• Do NOT overlap combustible materials onto

¿ replace

front.

Install combustible materials up to speci

¿ ed clearances

on top front and side edges.

• Seal joints between the

¿ nished wall and ¿ replace top

and sides using only a 300° F minimum sealant.

¨

¨

Advertising
This manual is related to the following products: