REPLACING AN R4140M OR R4150M WITH START

INTERLOCKS WITH A BC7000L/PM720M2002

STEPS FOR CONVERSION

1. START INTERLOCKS BECOME PREIGNITION INTERLOCKS.

2. DISCONNECT DAMPER CONTROL WIRE FROM TERMINAL 10

CONNECT IT TO TERMINAL 11.

3. REMOVE JUMPER FROM TERMINAL BETWEEN TERMINAL 11

AND 12 (on some models).

4. IF LOW FIRE SWITCH IS NOT USED, CONNECT JUMPER WIRE

BETWEEN TERMINALS 8 AND 13.

5. JUMPER 8 TO

FOR 30-SECOND PREPURGE.

6. IF OLD CONTROL HAD 12 TO 11 JUMPERED, ADD A JUMPER

FROM 12 TO 16.

E1235B