List of Holding Registers

Network Data

Func.

Code

Name

R/W

Description

Reg.

Range

Res.

C144

Terminal [11] ON delay

R/W Range is 0.0 to 100.0 sec.

1153h 0 to 1000 0.1 sec

C145

Terminal [11] OFF delay

R/W Range is 0.0 to 100.0 sec.

1154h 0 to 1000 0.1 sec

C148

Output relay ON delay

R/W Range is 0.0 to 100.0 sec.

1157h 0 to 1000 0.1 sec

C149

Output relay OFF delay

R/W Range is 0.0 to 100.0 sec.

1158h 0 to 1000 0.1 sec

Note 1:

Assume that the inverter current rating is 10000 (for C041).

The following table lists the holding registers for the “H” Group Motor Constants.

List of Holding Registers

Network Data

Func.

Code

Name

R/W

Description

Reg.

Range

Res.

H003

Motor capacity

R/W

1165h

0 to 13



H203

Motor capacity, 2nd
motor

R/W

0…0.20kW
1…0.37kW
2…0.40kW
3…0.55 kW
4…0.75 kW
5…1.10 kW
6…1.50 kW
7…2.2 kW
8…3.0 kW
9…3.7 kW
10…4.0 kW
11…5.5 kW
12…7.5 kW
13…11.0kW

1541h

0 to 13



H004

Motor poles setting

R/W

1166h

2, 4, 6, 8

1 pole

H204

Motor poles setting, 2nd
motor

R/W

Four selections:
2 / 4 / 6 / 8

1542h

2, 4, 6, 8

1 pole

H006

Motor stabilization
constant

R/W

1168h

0 to 255

1

H206

Motor stabilization
constant, 2nd motor

R/W

Motor constant (factory set),
range is 0 to 255

1544h

0 to 255

1

B

39

Appe

ndix B

B 39

Appendix B