Guidelines for installing the chimney connector – Heartland The Artisan User Manual

Page 10

Advertising
background image

0

Connection Requirements

1. The chimney connector should be made of 24 gauge or

thicker sheet metal and should be 6” in diameter.

2. The last section of the chimney connector starting from

the stove should be screwed to the flue collar of the stove

with at least 3 self -tapping screws. Individual sections of

the chimney connector must be screwed together with at

least three sheet metal screws. The last section should

be securely attached to the chimney. Be sure there are

no “weak links” in the system.

3. The crimped ends of pipe sections should point downward

toward the stove so that any soot or creosote that falls

from the inside of the pipe will be funnelled into a clean

out or fall into the stove.

4. A horizontal run of chimney connector should be no

longer than 10 inches. A vertical run of stovepipe to a

prefabricated metal chimney should be no longer than

8 ft.

5. Do not pass the stovepipe chimney connector through

a combustible wall if it can be avoided. If this cannot be

avoided, follow the recommendation in CSA B365 in

Canada and NFPA 211 in the U.S., recommendation on

Wall Pass-Throughs.

6. Do not use single wall chimney connector as an outside

chimney.

7. Never pass a chimney connector through a combustible

ceiling.

8. The whole chimney connector should be exposed and

accessible for inspection and cleaning.

9. Galvanized stovepipe should not be used. When exposed

to the temperatures reached by smoke and exhaust

gases, galvanized pipe may release toxic fumes.

10. Horizontal runs of chimney connector should slope upward

1/4” per foot going from the stove toward the chimney.

11. During a chimney fire, the chimney connector may vibrate

violently. The connector must be securely attached to

the pipe and chimney, and individual sections must be

securely attached together.

12. This stove is not to be connected to an air distribution

horizontal Connection

The Heartland Artisan has the ability to connect stove pipe

out the top of the flue box vertically or out the back of the

flue box horizontally.

To run horizontally out the back of the flue box, remove

plate from rear of the flue box by loosening 5/16" nut on

the inside of the flue box hold down. Ensure rope gasket

insulation is intact on plate perimeter. Remove flue collar

from top of flue box by removing one screw and small

bracket. Set screw and bracket aside and loosen only

screw on opposite side.Flue collar can now be removed.

Interchange position of the removed flue collar and the flue

plate..Ensure the two tabs on the flue collar are securely

tightened inside flue box. Ensure rope gasket is tight on

plate for proper seal.Tighten 5/16" nut on plate hold down.

Make sure all connections are tightly sealed.

All horizontal stove pipe must slope slightly upwards a

minimum of 1/4 per foot (6mm per 0.3m). This slope is

to allow water vapour to drain back into the stove. All

connections must be tight and secured by a minimum

of three equally spaced sheet metal screws. Under no

condition should the chimney connector have more than

one 90 degree bend or two 45 degree bends.

Guidelines for Installing the Chimney

Connector

The chimney connector is a single-wall pipe or a listed and

approved double-wall pipe that connects the stove to the

chimney. Approved clearances change according to what

type of chimney connector you use. Consult the clearances

section of this manual for the proper clearances. The stove's

flue collar accepts only 6" chimney connector.

Follow the chimney manufacturer's direction for installation.

We recommend that prior to installing your stove into a

masonry chimney, you have the chimney inspected by

a qualified mason. Note: Canadian installations into a

masonry chimney MUST be fully relined with a listed solid

fuel chimney liner.

Advertising