14

Control performance:

Two-step

Display accuracy:

± 0.5 K internal, ±1 digit, at 25 °C

Operating conditions:

0 to 50 °C, 30 to 85 % R.H.,
excluding dew

Storage temperature:

–20 to +80 °C

Data back-up:

Non-volatile memory (EEPROM)

Sensor:

1 PTC

– Sensor cable length:

2.5 m

– Range where cable

–30 °C to +80 °C not fixed

can be used:

–40 °C to +80 °C fixed

– Sensor accuracy:

±2 %

Housing:

PCR-100: L x W x H = 85 x 70 x 61 mm
PCR-110: L x W x H = 70 x 74 x 32 mm

ABS plastic, self-extinguishing
(UL 94 V0)

Protective rating:

Housing: IP 20, Front panel: IP 52
Class of protection 2

Terminals:

10 A screw-type terminal strips,
with wire protection,
tightening torque 0.6 Nm
Max. core cross section 1.5 mm

2

Weight:

PCR-100: Approx. 330 g (inc. sensor).

PCR-110: Approx. 240 g (inc. sensor).

Only operate the unit in dry places.

Errors in the technical data are excepted. We reserve the right to make
changes without prior notice.