6 finishing, Figure 33 – Hearth and Home Technologies SL-550TRSI-AUE User Manual

Page 25

Advertising
background image

25

Heat & Glo • SL-550TRSI-AUE • 2079-902 Rev. B • 7/06

Figure 33.

1.6 FINISHING

The minimum clearance to combustibles are 0 from
the sides, floor, back and top (these clearances are
defined by the standoffs). The minimum distance to the
perpendicular side wall extending past the appliance
front is 2-inches (51mm). Clearance to a mantelpiece
is shown in Figure 33.

IF JOINTS BETWEEN THE FINISHED WALLS AND
THE FIREPLACE SURROUND (TOP AND SIDES)
ARE SEALED, A 300° F (149°C). MINIMUM SEAL-
ANT MATERIAL MUST BE USED. THESE JOINTS
ARE NOT REQUIRED TO BE SEALED. ONLY NON-
COMBUSTIBLE MATERIAL (USING 300° F. (149°C)
MINIMUM ADHESIVE, IF NEEDED) CAN BE AP-
PLIED AS FACING TO THE FIREPLACE SUR-
ROUND. SEE FIGURE 33.

TOP SEAL

JOINT

SIDE SEAL

JOINT

1/2”

(13mm)

0”

FINISH MATERIAL

MAY BE COMBUSTIBLE

- TOP AND SIDES

OF UNIT

CEILING

31”

(787mm)

12”

(305mm)

11”

(279mm)

10”

(254mm)

9”

(229mm)

8”

(203mm)

7”

(178mm)

6”

(152mm)

5”

(127mm)

4”

(102mm)

3”

(76mm)

2”

(51mm)

TOP FRONT EDGE

OF FIREPLACE

NON-COMBUSTIBLE

BOARD

2” (51mm)

3” (76mm)

4” (102mm)

5” (127mm)

6” (152mm)

7” (178mm)

8” (203mm)

9” (229mm)

10” (254mm)

11” (279mm)

12” (305mm)

Advertising