5

69-0780

Action

System Response

Primary limit switch string closes.

• Circulating fan turns off after the selected heat fan off delay timing.
• LED stops flashing.
• Normal operation resumes.

Primary limit switch string is open

• Combustion air blower, circulating fan and ignition system are de-energized.

for more than 150 seconds (on each

• Control goes into lockout mode.

of three consecutive cycles).

• LED flashes four times.
• Control remains in lockout until 24V power is removed and reapplied (control

is reset).

• LED stops flashing.
• Normal operation resumes.

Burner limit opens.

• Thermostat and ignition system are de-energized and gas valve closes.
• Combustion air blower and circulating fan heat speed are energized.
• LED flashes once.

Burner limit closes.

• Combustion air blower remains energized for postpurge timing.
• The circulating fan remains energized for the selected delay off timing.
• LED stops flashing.
• Normal operation resumes.

Electronic air cleaner is connected.

• Electronic air cleaner is energized when the circulating fan heat or cool speed

(Connector to 120 Vac electronic

is energized.

air cleaner.)

Humidity control is connected.

• Humidifier is energized when combustion air blower is energized.

(Connector to 120 Vac humidifier.)

ST9141A1002 Operating Sequence (Continued)