Single-pole phase test, Voltage test with rcd trip test – Fluke Fiber Viewer FT140 User Manual

Page 8

Advertising
background image

Single-Pole Phase Test

• To carry out single-pole phase tests ouch the

Accessible electrode (11) and connect instru-

ment test probes to unknown contact.

• The single-pole phase test starts at an AC

voltage of approx. 100V (pole > 100V AC).

• When using single-pole phase tests to deter-

mine external conductors the display function

may be impaired under certain conditions

(e.g. for insulating body protective equipment

on insulation locations).

• The single-pole phase testing is not appro-

priate to determine whether a line is live or

not. For this purpose, the double-pole voltage

test is always required.

The LED (5) is illuminated in the display.

Voltage Test with RCD Trip Test

(not T140 VDE)

During voltage tests in systems equipped with

RCD circuit breakers, a RCD switch can be trip-

ped at a nominal residual current of 10mA or

30mA by measuring the voltage between L and

PE.

The RCD trips.

To avoid RCD tripping a test has to be car-

ried out between L and N during approx.

5s. Immediately afterwards, voltage tes-

ting between L and PE can be carried out

without RCD tripping.

Fluke T100/120/140
Users Manual

8

Advertising
This manual is related to the following products: