The Fluke 1750 Power Recorder is a comprehensive yet easy to use system for power

quality investigations. The 1750 Power Recorder, referred to hereafter as simply “the

Recorder or the Product,” consists of a power recorder instrument, a wireless handheld

Personal Digital Assistant (PDA) for control and setup, and a powerful yet easy to use PC

application, Power Analyze. Four 400 A current probes are provided as standard

equipment (not included in Basic version). A wide range of flexible and clamp-on current

probes are available from Fluke.
Key features of the 1750 Power Recorder are:

No PC needed for setup

Using the included wireless-enabled Personal Digital Assistant (PDA) as a controller,

you do not need a PC to configure the Recorder, troubleshoot connections, preview

data, or download the recorded data. Downloaded data goes onto the SD memory

card plugged into the 1750, not directly to the PDA. The range of the PDA with the

wireless link is about 5 meters (16 feet) from the Recorder. This range is dependent

on the electrical interference in the location.

Simplified test lead connections to the power network

Simply connect a voltage probe to a conductor on each phase that you want to record.

On the current inputs, the Recorder automatically identifies what type of probe is

connected. The Recorder then configures its measurement system appropriately for

the model of current probe you are using.

Connection diagrams for the supported power network configurations (delta, Wye,

and others) appear on the handheld PDA controller. Once you make connections, you

can view live readings and a phasor diagram on the PDA to confirm the connections.

If a phase channel is wired incorrectly, you can swap the phase to another channel by

changing an internal Recorder setting using the PDA, and then reconfirm correct

readings.

Internal Uninterruptible Power Supply (UPS)

An internal NiMH (Nickel-Metal-Hydride) battery pack and charging system

maintain data capture continuity through power interruptions of approximately

5 minutes or less.