Dimensions and clearances

Entire front of icemaker must be clear of obstructions/connections to allow removal.

1" (26mm) clearance above icemaker for service.

1" (26mm) minimum clearance on sides.

The intake and exhaust air grilles must provide at least 150 sq in (968 sq cm) of open area.

Air-cooled model HCC1000A icemakers – 18" (458mm) minimum clearance between discharge and air
intake-grilles.

G

L2

L1

Front View

Side View

Back View

Air intake

21.05" (535mm)

23.50"

(597mm)

21.28" (541mm)

22.8" (580mm)

NEMA 6-15
right angle

3/8" OD push-in water inlet

6.95"

(177mm)

15.56"

(395mm)

1.75" (45mm)
min. req'd

1/4" FPT
condenser drain

1/4" FPT
condenser inlet

3/4" MPT drain

2.53

(65mm)

Air exhaust

26.63" (677mm)

Ice transport hose connection

2.43" (62mm)

Air exhaust
both sides