Falcon RACKMOUNT UPS PLUS FN4KRM-2TX User Manual

Page 10

Advertising
background image

4.2 UPS Input Power Requirements

a.

VERIFY THE PROPER UPS INPUT POWER IS AVAILABLE (for each UPS installed)

FN3KRM-2TXI Input

--

Hardwire, 208-240Vac, 50/60Hz, 20A, single-phase, 2 wire plus ground

FN4KRM-2TXI Input

--

Hardwire, 208-240Vac, 50/60Hz, 30A, single-phase, 2 wire plus ground

FN5KRM-2TXI Input

--

Hardwire, 208-240Vac, 50/60Hz, 30A, single-phase, 2 wire plus ground

FN6KRM-2TXI Input

--

Hardwire, 208-240Vac, 50/60Hz, 40A, single-phase, 2 wire plus ground

FN8KRM-2TXI Input

--

Hardwire, 208-240Vac, 50/60Hz, 50A, single-phase, 2 wire plus ground

FN10KRM-2TXIInput

--

Hardwire, 208-240Vac, 50/60Hz, 65A, single-phase, 2 wire plus ground

4.3 UPS Input/Output Requirements

a.

VERIFY THE INPUT AND OUTPUT WIRING REQUIREMENTS

FN3KRM-2TXI Wiring Type -- THHN, 600V, insulated solid copper wire

Gage

-- Input, 12 awg. - Output, 10 awg.

Terminal Block Screw Torque -- 20 inch-pounds
Required Branch Rated input circuit breaker -- 20A (40A with 3 external battery charger module

options installed)

Required Branch Rated output circuit breaker -- 20A

FN4KRM-2TXI Wiring Type -- THHN, 600V, insulated solid copper wire

Gage

-- Input, 10 awg. - Output, 8 awg.

Terminal Block Screw Torque -- 20 inch-pounds
Required Branch Rated input circuit breaker -- 30A (50A with 3 external battery charger module

options installed)

Required Branch Rated output circuit breaker -- 30A

FN5KRM-2TXI Wiring Type -- THHN, 600V, insulated solid copper wire

Gage

-- Input, 10 awg. - Output, 8 awg.

Terminal Block Screw Torque -- 20 inch-pounds
Required Branch Rated input circuit breaker -- 30A (50A with 3 external battery charger module

options installed)

Required Branch Rated output circuit breaker -- 30A

FN6KRM-2TXI Wiring Type -- THHN, 600V, insulated solid copper wire

Gage

-- Input, 8 awg. - Output, 4 awg.

Terminal Block Screw Torque -- 25-30 inch-pounds
Required Branch Rated input circuit breaker -- 40A (60A with 3 external battery charger module

options installed)

Required Branch Rated output circuit breaker -- 40A

FN8KRM-2TXI Wiring Type -- THHN, 600V, insulated solid copper wire

Gage

-- Input, 8 awg., 75C copper wire - Output, 4 awg.

Terminal Block Screw Torque -- 11 inch-pounds
Required Branch Rated input circuit breaker -- 50A (60A with 3 external battery charger module

options installed)

Required Branch Rated output circuit breaker -- 50A

FN10KRM-2TXI Wiring Type -- THHN, 600V, insulated solid copper wire

Gage

-- Input, 8 awg., 75C copper wire- Output, 4 awg.

Terminal Block Screw Torque -- 11 inch-pounds
Required Branch Rated input circuit breaker -- 65A (70A with 3 external battery charger module

options installed)

Required Branch Rated output circuit breaker -- 65A

CAUTION - A disconnect switch shall be provided by others for ac output circuit. To reduce the risk
of fire, connect only to a circuit provided with branch circuit
overcurrent protection for 30 amperes rating in accordance with the National Electric Code,
ANSI/NFPA 70

CAUTION - To reduce the risk of fire, unit input connect only to a circuit provided with branch circuit
overcurrent protection for 40 amperes rating in accordance with the National Electric Code,
ANSI/NFPA 70”.

10