4.4 UPS Output Rating Details

a.

VERIFY THE LOAD TO BE CONNECTED DOES NOT EXCEED THE UPS OUTPUT
RATING for the single or combined paralleled UPS units.

(1) FN3KRM-2TXI

Not N+1

Hardwire, 120/240Vac, 2,100W, split-phase, 3 wire plus ground

(2) FN3KRM-2TXI

Not N+1

4,200W

N+1

2,100W

(3) FN3KRM-2TXI

Not N+1

6,300W

N+1

4,200W

(4) FN3KRM-2TXI

Not N+1

8,400W

N+1

6,300W

1) FN4KRM-2TXI

Not N+1

Hardwire, 120/240Vac, 2,800W, split-phase, 3 wire plus ground

(2) FN4KRM-2TXI

Not N+1

5,600W

N+1

2,800W

(3) FN4KRM-2TXI

Not N+1

8,400W

N+1

5,600W

(4) FN4KRM-2TXI

Not N+1

11,200W

N+1

8,400W

(1) FN5KRM-2TXI

Not N+1

Hardwire, 120/240Vac, 3,500W, split-phase, 3 wire plus ground

(2) FN5KRM-2TXI

Not N+1

7,000W

N+1

3,500W

(3) FN5KRM-2TXI

Not N+1

10,500W

N+1

7,000W

(4) FN5KRM-2TXI

Not N+1

14,000W

N+1

10,500W

(1) FN6KRM-2TXI

Not N+1

Hardwire, 120/240Vac, 4,200W, split-phase, 3 wire plus ground

(2) FN6KRM-2TXI

Not N+1

8,400W

N+1

4,200W

(3) FN6KRM-2TXI

Not N+1

12,600W

N+1

8,400W

(4) FN6KRM-2TXI

Not N+1

16,800W

N+1

12,600W

1) FN8KRM-2TXI

Not N+1

Hardwire, 120/240Vac, 5600W, split-phase, 3 wire plus ground

(2) FN8KRM-2TXI

Not N+1

11,200W

N+1

5,600W

(3) FN8KRM-2TXI

Not N+1

16,800W

N+1

11,200W

(4) FN8KRM-2TXI

Not N+1

22,400W

N+1

16,800W

1) FN10KRM-2TXI

Not N+1

Hardwire, 120/240Vac, 7000W, split-phase, 3 wire plus ground

(2) FN10KRM-2TXI

Not N+1

14,000W

N+1

7,000W

(3) FN10KRM-2TXI

Not N+1

21,000W

N+1

14,000W

(4) FN10KRM-2TXI

Not N+1

28,000W

N+1

14,000W

11