Ce standard, Gas connection pipe sizes, Ensure the combustion air supply airflow is 2m – Frymaster 47 Series User Manual

Page 14

Advertising
background image

2-6

BE

I2E+(S)

I3P

G20/G25

G31

20/25

37

DE

I2 ELL

13P

G20/G25

G31

20
50

FR

II2Esi3P

G20/G25

G31

20/25

37 ET 50

LU

I2E

G20/G25

20/25

ES

II2H3P

G20
G31

20

37 ET 50

NL

II2L3P

G25
G31

25
50

IE-PT-GB

II2H3P

G20
G31

20
37

DK-GR-IT

I2 H

G20

20

CE Approved Gas Categories

Country

Category

Gas

Pressure

(mbar)

The size of the gas line used for installation is very important. If the line is too small, the gas
pressure at the burner manifold will be low. This may cause slow recovery and delayed ignition.
The incoming gas supply line should be a minimum of 1½” (38 mm) in diameter. Refer to the chart
below for the minimum sizes of connection piping.

Gas Connection Pipe Sizes

(Minimum incoming pipe size should be 1 1/2" (38 mm))

Natural

3/4" (19 mm)

1" (25 mm)

1 1/4" (33 mm)

Propane

1/2" (13 mm)

3/4" (19 mm)

1" (25 mm)

Manufactured

1" (25 mm)

1 1/4" (33 mm) 1 1/2" (38 mm)

Gas

Single Unit

2 - 3 Units

4 or more

units*

* For distances of more than 20 feet (6 m) and/or more than 4
fittings or elbows, increase the connection by one pipe size.

Before connecting new pipe to your unit, the pipe must be thoroughly blown out to remove any
foreign particles. If these foreign particles get into the burner and controls, they will cause improper
and sometimes dangerous operation.

CE Standard

Ensure the combustion air supply airflow is 2m

3

/h times the kW rating of the fryer.

(See the rating plate affixed to the fryer door for the kW rating.)


1. Connect the quick-disconnect hose to the fryer quick-disconnect fitting under the front of the

fryer and to the building gas supply-line.

NOTE: Some fryers are configured for a rigid connection to the gas supply line. These units are
connected to the gas supply line at the rear of the unit.