Location – FMI VENT FREE UNIVERSAL MASONRY FIREBOX MM39/44/49VF User Manual

Page 7

Advertising
background image

6

Location

Note: You may need to provide combustion and ventilation air

from an outside source to adequately satisfy local codes so

avoid installing a combustion air inlet where the opening could

be blocked by snow, bushes or other obstacles. Note that the

access for outside air inlet is located on the right hand side of

the fireplace.

Internal

Wall

Installation

Full

Projection

Installation

Flush

Installation

Corner

Installation

Figure 3

A flush installation is recommended where living space is

limited or at a premium. Check local codes for any restrictions.

W

H

D

Figure 4

Model

W

H

D

MM39VF

43”

41”

28”

MM44VF

48”

41”

28”

MM49VF

53”

41”

28”

Projected installations can extend any distance into the room.

A projection may be ideal for a new addition on an existing,

finished wall.

Corner installations make use of space that may not normally

be used and provides a wider and more efficient range for heat

disbursement.

An internal wall installation provides a discreet option for

room separation and can also be ideal as an addition to an

existing wall.

IMPORTANT: Vent-free heaters add moisture to the air. Installing

a fireplace in rooms without enough ventilation air may cause

mildew to form from too much moisture.

IMPORTANT: Make sure the fireplace is level. If the fireplace is

not level, the log set will not work properly.

Attention: You may need a building permit to install a Grand

Meridian fireplace. Check with the local jurisdiction before you

get started.

Supporting Floor Systems

Floor Framing

It is important to take into consideration that the load for the

Grand Meridian Fireplace is considerable, but, more important,

that it is a dead load that will have to be absorbed by a relatively

small amount of existing floor space.

It is the ultimate responsibility of the installer to ensure that

proper concrete slab supports are used.

WARNING to the licensed design professional and/or building

contractor: It is your responsibility to be certain that the Grand

Meridian can be properly supported by the combustible floor

system on which the fireplace will rest.

For fireplace support foundations installed on concrete refer to

Appendix I and II (

pages 17 & 18) for specific instructions.

Rebar locations

Lay-out the position of the fireplace and drill holes where

the rebar will be located. Secure the #3 rebar 4 inches into the

concrete foundation with ITW Epoxy or Simpson Epoxy. Follow

manufacturer’s instructions for installation of rebar into slab.

Wood Floor

Anchorage of fireplace to wood floor construction is required.

Refer to

Figure 8 for anchorage dimensions. Four anchors are

required to attach to the sub-flooring framing.

Crawl Space or Upper Floor:
For installation of firebox over combustible crawl spaces or

upper floors, anchorage of the firebox is required. Illustrations

of examples of possible anchorage methods are shown in

Figures 5 thru 7 depending upon the type of floor framing. Final

method of anchorage is to be determined by licensed design

professional.

Advertising