FMI VENT FREE UNIVERSAL MASONRY FIREBOX MM39/44/49VF User Manual

Page 8

Advertising
background image

7

For conventional framing, where the floor joists are parallel

with the sides of the firebox, the addition of floor joists to align

with the anchor brackets allows the brackets to be directly

connected to the floor joists.

Note that additional floor joists may be required to support

the weight of the firebox and chimney. Where the floor joists run

parallel to the front of the firebox, anchorage can be accomplished

in like manner as shown in Figure 5 using blocking between the

floor joist.

For floors supported by I-Joists, the method of anchorage is

illustrated in Figures 6 and 7. Figure 10 illustrates the general

arrangement of anchorage to floor framing.

It is important to take into consideration that the load for the

Grand Meridian Fireplace must be considered as additional

dead load that will have to be supported by the floor framing.

Additional floor joists or I-joists may be required as determined

by the licensed design professional.

The dead weights for the fireplace are noted in Table I. It is

the task and responsibility of the general contractor/installer to

see that the proper reinforcement for weight loads are made by

a licensed design professional prior to the fireplace installation.

As stated above, it is desirable to place additional framing

for alignment of anchor rods. Refer to Figure 10 for anchor rod

locations.

Figure 5

Floor Sheathing

not shown for

clarity

Anchor Bracket

Assembly

EXAMPLE ONLY

2X FLOOR JOIST

2X FLOOR JOIST

A35 Brackets

(16 required)

I-Jo

ist

Simpson

Strong-Tie

A-35 or

equivalent

Figure 6

I-Joist Anchoring

Top View

Example Only

I-JOISTS

Anchor

Brackets

Figure 7

I-Joist

Anchoring

Bottom

View

Example Only

Advertising