Duct fittings, Advance planning – GE Monogram ZVC36 User Manual

Page 10

Advertising
background image

10

Advance Planning

DUCT FITTINGS

This Hood Must Use an

8

Round Duct. It Can

Transition to a

3-1/4

x 12

Duct.

Use this chart to compute
maximum permissible lengths
for duct runs to outdoors.

NOTE: Do not exceed maximum
permissible equivalent lengths!

Maximum duct length:
100 foot for range hoods.

Flexible ducting:
If flexible metal ducting is used,
all the equivalent feet values in
the table should be doubled.
The flexible metal duct should
be straight and smooth and
extended as much as possible.

DO NOT use flexible plastic
ducting.

NOTE: Any home ventilation
system, such as a ventilation hood,
may interrupt the proper flow of
combustion air and exhaust
required by fireplaces, gas
furnaces, gas water heaters and
other naturally vented systems.
To minimize the chance of
interruption of such naturally
vented systems, follow the
heating equipment manufacturer’s
guidelines and safety standards
such as those published by NFPA
and ASHRAE.

Total

Equivalent

Quantity Equivalent

Duct Piece

Dimensions

Length*

Used

Length

Round,

1 ft.

straight

(per foot
length)

3-1/4

x 12

1 ft.

straight

(per foot
length)

90° elbow

17 ft.

45° elbow

10 ft.

3-1⁄4

x 12

90° elbow

43 ft.

3-1/4

x 12

45° elbow

26 ft.

3-1/4

x 12

90° flat elbow

102 ft.

8

round to

3-1/4

x 12

transition

2 ft.

3-1/4

x 12

to 8

round transition

5 ft.

8

round

to 3-1/4

x 12

transition 90° elbow

6 ft.

3-1/4

x 12

to 8

round transition 90° elbow 13 ft.

Round
wall cap
with damper

32 ft.

3-1/4

x 12

wall cap

with damper

75 ft.

Round
roof cap

44 ft.

Total Duct Run

*Actual length of straight duct plus duct fitting

equivalent. Equivalent length of duct pieces are
based on actual tests conducted by GE Evaluation
Engineering and reflect requirements for good
venting performance with any ventilation hood.