Generac PRIMEPACT 50 04164-3 User Manual

Page 31

Advertising
background image

29

2.5.3 VAPOR

WITHDRAWAL

‹

LP gas is stored in pressure tanks as a liquid. The gas systems

used with these generators were designed only for vapor with-

drawal type systems. Vapor withdrawal systems use the gas

vapors that form above the liquid fuel in the tank. Do NOT attempt

to use the generator with any liquid withdrawal type system.

2.5.4 PRIMARY

REGULATOR

‹

Gas pressure delivered to the solenoid valve must be properly

regulated by means of a primary gas regulator. Mount the primary

regulator at the gas tank outlet or in the supply line from the gas

tank. The following rules apply:

For best results, the primary regulator supplies gaseous fuel to

the secondary regulator at 11 inches water column. Do NOT

exceed 14 inches water column.

The installer must be sure the primary regulator is rated at

sufficient gas flow to operate the generator plus all other gas

appliances in the circuit.

NOTE:

Recommended MINIMUM gas flow rate for all air-cooled gen-

erators is 67 cubic feet per hour.
If an existing primary gas regulator does not have a sufficient

flow capacity for the generator and other gas appliances in the

circuit, (a) install a primary regulator with adequate flow rate,

or (b) install a separate regulator only and rated at least 67

cubic feet per hour. The inlet side of any primary regulator that

supplies the generator must connect directly to a gas pressure

tank. Do NOT tee the generator line into a gas circuit feeding

other areas.

2.5.5 GASEOUS

CARBURETION

‹

LP gas vapors should be supplied to the secondary regulator inlet

at about 11 inches water column (positive pressure). The engine

pistons draw air in during the intake stroke (Figure 2.16). This air

passes through a carburetor venturi, which creates a low pressure

that is proportional to the quantity of air being pumped. The low

pressure from the carburetor venturi acts on the regulator dia-

phragm to pull the diaphragm toward the source of low pressure.

A lever attached to the diaphragm opens a valve to permit gas glow

through the carburetor.

Figure 2.16 – LP Gas Carburetion Diagram

The greater the airflow through the carburetor venturi, the lower the

pressure at the venturi throat. The lower the pressure at the venturi

throat, the greater the diaphragm movement, and the greater the

movement of the regulator valve. The more the regulator valve

opens, the greater the gas flow that is proportional to airflow

through the generator.
The following facts about the secondary regulator must be empha-

sized:

The regulator must be sensitive to venturi throat pressure

changes throughout the operating range.

The regulator must be properly adjusted so it will stop the flow

of gas when the engine is not running (no air flow through the

carburetor).

The slightest airflow (and vacuum in the venturi throat) should

move the regulator valve off its seat and permit gas to flow.

2.5.6 FUEL SUPPLY LINES

‹

LP gas lines must be accessible, but protected against possible

damage.

Do NOT connect electrical wiring to any LP gas fuel line or run

wiring alongside the lines.

Route gas lines away from hot engine exhausts.

Retain gas lines with metal clamps that do not have sharp

edges.

Install an approved length of flexible hose between the gaseous

fuel solenoid valve and rigid fuel supply lines. The flexible line

must be nonmetallic, nonorganic and nonconductive. It must be

approved for use with LP gas.

2.5.7 EXCESS FLOW VALVE

‹

LP gas tanks should have an excess flow valve, according to

NFPA 501C, Paragraph 3-4.4. This valve and the gas lines must

be carefully sized so the valve will close when a fuel line is severed

or broken. Consult the Natural-LP Gas Association for information

and limitations of excess flow valves.
Manual shutoff valves on the supply tank and elsewhere in the sys-

tem must be fully open when operating the generator. The excess

flow valve functions properly only if all valves are fully open.

2.5.8 LEAKAGE

TESTS

‹

Do not place the generator into service until the gas system has

been properly tested for leaks. To test the system, a separate

source of 12 volts DC is needed to open the gaseous fuel solenoid

valve.
The leak test must comply fully with NFPA, Paragraph 318. All con-

nections, hoses, valve regulators, fittings, and other fuel system

parts must be tested under gas or air pressure of not less than

90 psi (620 kPa), while using soap and water or an equivalent

solution to check for leaks. Other approved methods of testing for

leaks may be used, if appropriate. DO NOT USE ANY FLAME TO

TEST FOR LEAKS.

Section 2 – Installation

Recreational Vehicle Generator

Advertising
This manual is related to the following products: