6 stopping the generator, 7 applying loads to generator, 8 summer/winter heat riser system – Generac PRIMEPACT 50 04164-3 User Manual

Page 12

Advertising
background image

10

Section 2 – Operation

Recreational Vehicle Generator

NOTE:

If starting from the generator control panel, turn OFF loads

by setting the generator’s main circuit breaker to the OFF (or

OPEN) position. If starting from a remote panel, turn OFF loads

using the means provided in the vehicle (such as a main circuit

breaker). Electrical load circuits will be turned ON after the

generator has started, stabilized and warmed up.
2. If the engine has not been started in more than two weeks,

press the Fuel Pump Primer switch and hold it for about 10 to

15 seconds to prime the fuel system. However, if the engine

is warm, skip Step 2.

3. Hold the engine Start/Stop switch in the START position to

crank the engine. Release the switch when the engine starts.

If the engine does not start after it has been

cranking for 15 seconds, release the Start/Stop

switch and try again. Holding the switch for

longer than 15 seconds can damage the starter

motor.

4. Let the engine run at no-load for a few minutes to stabilize and

warm up.

5. Turn ON electrical loads using the means provided (such as a

main circuit breaker or transfer switch).

2.6 STOPPING THE GENERATOR

1. Turn OFF all electrical loads using the means provided (such

as a main circuit breaker or transfer switch).

2. Let generator run at no-load for a few minutes, to stabilize inter-

nal engine generator temperatures.

3. Place the Start/Stop switch in its STOP position.

2.7 APPLYING LOADS TO

GENERATOR

When applying electrical loads to the generator, observe these

guidelines:

Before applying electrical loads, let the generator stabilize and

warm up for a minute or two.

DO NOT overload the generator.

2.7.1 LETTING THE ENGINE STABILIZE

‹

The generator supplies correct rated voltage only at the proper

governed speed. Some electrical appliances may be extremely

sensitive to voltage. Incorrect voltages can damage such appli-

ances.
If electrical loads are applied at reduced operating speeds, such

loads imposed on the engine when sufficient power is not available

may shorten engine life. Never turn ON electrical loads until after the

generator engine has started and stabilized at no-load.

2.8 SUMMER/WINTER HEAT

RISER SYSTEM

Under certain weather conditions, it is possible for ice to form

in the venturi area of the carburetor. This condition can be very

dangerous because it can prevent the governor system from func-

tioning properly, which results in a “runaway” engine.
The most common weather conditions leading to this problem are

temperatures in the range of 25° F to 35° F (-4° C to 1.7° C), along

with high humidity. This ice formation also can be attributed to the

load being applied during these weather conditions. Generators

running with no-load or light loads applied usually have the most

problems.
The Summer/Winter Lever (Figure 2.3) should be in the WINTER

position for ambient temperatures below 40° F (4.4° C) and in the

SUMMER position for ambient temperatures above 40° F (4.4°

C).

Figure 2.3 – Heat Riser System

When the heat riser is in the SUMMER (down) position (Figure

2.2), air is drawn into the air cleaner from the upper intake tube.
When the heat riser is in the WINTER (up) position, air is drawn

from the lower intake tube, which is positioned to draw the heated

air near the exhaust manifold.
To prevent carburetor icing, the owner/operator should physically

position the heat riser to the proper position dependent on the

temperature.

Advertising
This manual is related to the following products: