32

Route conduit so it does not interfere with generator move-

ment.

If using metallic conduit, vapor seal the end of the conduit

where it enters the junction box. Do this because flexible metal-

lic conduit is not vaporproof along its entire length.

2.7.5 ISOLATING DIFFERENT POWER SOURCES

‹

Connections from the junction box must terminate in a double-

pole, double-throw transfer switch (Figure 2.18). An alternate

method for isolating different power sources is by using an isolat-

ing receptacle (Figure 2.19). Whichever method is use, be certain

that both power sources are NOT connected at the same time.

2.7.6 POWER SUPPLY CORD

‹

The power supply cord must comply with all applicable codes,

standards and regulations. It must be large enough to handle the

full amperage to which it will be subjected.

2.7.7 GROUND FAULT CIRCUIT INTERRUPTERS

‹

The National Electrical Code (NFPA 70, 551-7) requires that ground

fault circuit interrupters (GFCIs) on all external and some internal

electrical receptacles be installed. Contact the manufacturer or

dealer for recommendations.

2.8 BATTERY INSTALLATION

2.8.1 RECOMMENDED

BATTERY

‹

Install a battery that meets the following requirements:

The battery must be a 12-volt, automotive type storage bat-

tery.

For prevailing ambient temperatures above 32° F (0° C), use

a battery rated 70 amp-hours and capable of delivering 400

cold-cranking amperes.

For prevailing ambient temperatures below 32° F (0° C), use

a battery rated 95 amp-hours and capable of delivering 400

cold-cranking amperes.

NOTE:

If the battery is to be used to power other vehicle accessories,

as well as start the generator, a battery with a larger capacity

may be needed.

2.8.2 BATTERY

CABLES

‹

Using battery cables that are too long or too small in diameter may

cause a drop in voltage, which causes starting problems. For the best

cold weather starting, the voltage drop between battery terminals and

the generator connection point should not exceed 0.12 volts per 100

amperes of cranking current.

Section 2 – Installation

Recreational Vehicle Generator

Figure 2.18 – Transfer Switch Isolation Method