11.8 Testing Multiple Outlets for VDE 0702 (optional EL1 adapter)
➭ up to version 5.10:

Do not select “WITH EL1” in the initial menu. The following must
appear in the line: Ext. Cable – WITH EL1. “Manual sequence” must be
selected.

➭ from version 5.11 onwards:

Select “X

WITH EL1” in the initial menu. The following must

appear in the line: Ext. Cable X WITH EL1. “Manual sequence” must be
selected.

➭ A visual inspection must always be performed. It may thus be

necessary to unreel the cable from its drum or reel.

➭ Protective conductor resistance measurement: Contact the first outlet

with the EL1 adapter. Each time you are ready to contact the next
outlet, press the

key to repeat the test.

➭ After measurement has been completed for all outlets, reinsert the test

probe in order to continue with the performance of subsequent tests
as described in chapter 11.6.