7 out of service procedure, 8 fuel pipe sizing – Generac 004912-0 User Manual

Page 21

Advertising
background image

Generac

®

Power Systems, Inc.

19

1. The base frame of the unit contains an optional

fuel inlet location that is capped at the factory.
Check that it is secured in place. The same
applies for any access ports in the roof of the
enclosure. If any of these caps are missing,
contact a Generac Authorized Dealer.

2. Inside the generator set, the chance of rodent

entry into the control panel is greatly reduced by
the inclusion of adjustable wire connectors.
Check that the wire connector screws are tight,
thus closing off any gap between the access holes
and the wires.

4.7

OUT OF SERVICE PROCEDURE

4.7.1

REMOVAL FROM SERVICE

If the generator cannot exercise every seven days, and
it is to be out of service longer than 90 days, prepare
the generator for storage as follows:

1. Start the engine and let it warm up.
2. Close the fuel shutoff valve in the fuel supply line

and allow the unit to shut down.

3. Once the unit has shut down, it will signal a fault

on the control panel.

4. Set the Auto/Off/Manual switch to OFF and turn

off the utility power to the transfer switch.

5. While the engine is still warm from running,

drain the oil completely. Refill the crankcase with
SAE 15W-40 oil having API Service Class SD, SE
or SF. (See “Engine Oil Recommendations” in
Section 1.14)

6. Attach a tag to the engine indicating the viscosity

and classification of the oil in the crankcase.

7. Remove the spark plug(s) and spray fogging agent

into the spark plug(s) threaded openings.
Reinstall and tighten the spark plug(s).

8. Remove the battery and store it in a cool, dry

room on a wooden board. Never store the battery
on any concrete or earthen floor.

9. Clean and wipe the entire generator.

4.7.2

RETURN TO SERVICE

To return the unit to service after storage, proceed
as follows:

1. Verify that utility power is turned off to the

transfer switch and that the Auto/Off/Manual
switch is set to OFF.

2. Check the tag on the engine for oil viscosity and

classification. Verify that the correct recom-
mended oil is used in engine. See Section 1.14. If
necessary, drain and refill with the proper oil.

3. Check the battery. Fill all cells to the proper level

with deionized water. DO NOT USE TAP WATER
IN THE BATTERY. Remove the battery before
charging. Recharge the battery to 100 percent
state of charge, or, if defective, replace the battery
with a 12-volt DC Group 26/26R battery rated for
75 amp hours 525 CCA minimum @ 0° F.

4. Clean and wipe the entire generator.
5. Reconnect the battery. Observe battery polarity.

Damage may occur if the battery is connected
incorrectly.

6. Open the fuel shutoff valve.
7. Start the unit by moving the Auto/Off/Manual

switch to MANUAL. Allow the unit to warm up
thoroughly.

8. Stop the unit and set the Auto/Off/Manual switch

to AUTO.

9. Turn on the utility power to the transfer switch.
10. The generator is now ready for service.

4.8

FUEL PIPE SIZING

Refer to chart for proper sizing of fuel supply piping.
Insufficient fuel pipe size can cause hard starting,
poor engine performance and inability to carry load.

NG and LP Vapor Pipe Sizing Chart:

* Consumption in Cubic Feet Per Hour.

‹

‹

Section 4 — Maintenance

Centurion Liquid-cooled 15 kW and 25 kW Generators

Length of Pipe

Iron Pipe Size (IPS Inches)

in Feet

½"

¾"

1"

1 ¼"

1 ½"

2"

15

76

172

345

750

1,220

2,480

30

52

120

241

535

850

1,780

45

43

99

199

435

700

1,475

60

38

86

173

380

610

1,290

75

77

155

345

545

1,120

90

70

141

310

490

1,000

105

65

131

285

450

920

120

120

270

420

860

150

109

242

380

780

180

100

225

350

720

210

92

205

320

660

240

190

300

620

270

178

285

580

300

170

270

545

450

140

226

450

600

119

192

390

PERIODIC REPLACEMENT PARTS

Part Name

Generac’s Part Number

Oil Filter

# 0A45310244

Radiator Cap

# 046627

Air Cleaner

# 059402

Spark Plug

# 0A45310275

Advertising