8 voltage regulator adjustment, 1 break-in procedure, 2 using the auto/off/manual switch (figure 3.1) – Generac 04389-0 User Manual

Page 15

Advertising
background image

Generac

®

Power Systems, Inc. 13

Section 3 — Operation

Guardian Air-cooled 7 kW, 12 kW and 15 kW Generators

2.7.3

ADDITIONAL CORROSION
PROTECTION

Periodically spray all engine linkage parts and brack-
ets with corrosion inhibiting spray such as WD-40 or
a comparable product.

2.8

VOLTAGE REGULATOR
ADJUSTMENT

With the frequency between 61-62 Hertz, slowly turn
the slotted potentiometer (Figure 2.5) until line volt-
age reads 244-252 volts.

NOTE:

You must remove the access panel on top of the
control panel to adjust the voltage regulator.

Figure 2.5 – Voltage Adjustment Potentiometer

NOTE:

The voltage regulator is housed above the genera-
tor's control panel. The regulator maintains a volt-
age in direct proportion to frequency at a 2-to-1
ratio. For example, at 62 Hertz, line-to-neutral
voltage will be 124 volts.

3.1

BREAK-IN PROCEDURE

Once the unit has been installed and all electrical
checks have been made, it is strongly recommended
that the following “Break-in Procedure” be completed
to ensure correct generator operation in the future.
1. Set the generator’s Auto/Off/Manual switch to

AUTO.

2. Turn OFF the utility power supply to the transfer

switch using the means provided (such as a utili-
ty main line circuit breaker).

3. The unit will start, and the transfer switch will

transfer to standby.

4. Using the transfer switch’s built-in emergency

load center, turn on circuits to load the generator
to approximately 25% load and run the unit for
one hour.

5. Run the unit for one hour at 50 percent load.
6. Run the unit for one hour at 75 percent load.
7. Run the unit for one hour at 100 percent load.
8. Turn ON the utility power supply to the transfer

switch, which will allow the transfer switch to
transfer back to utility power. The unit will con-
tinue to run for one minute and then shut down.

9. Allow the unit to cool.
10. Drain the oil and remove the oil filter. Replace the

oil filter according to Section 4.4, “Changing the
Oil Filter” (Page 16). Replace the oil with synthet-
ic oil as recommended in Section 4.3, “Changing
the Engine Oil” (Page 15).

11. The generator is now ready for service.

3.2

USING THE AUTO/OFF/MANUAL
SWITCH (FIGURE 3.1)

3.2.1 “AUTO” POSITION

Selecting this switch position activates fully automatic

system operation. It also allows you to start and exercise

the engine every seven days with the setting of the exer-

cise timer (see Section 3.6, Page 14). This position also

is used for remote starting, when it is set up.

3.2.2 “OFF” POSITION

This switch position shuts down the engine. This

position also prevents automatic operation.

3.2.3 “MANUAL” POSITION

Set the switch to MANUAL to crank and start the

engine. Transfer to standby power will not occur

unless there is a utility failure.

Figure 3.1 – Generator Control Panel

Advertising
This manual is related to the following products: