3 engine governor gain adjustments – Generac 005030-0 (15kW) User Manual

Page 18

Advertising
background image

16

3.3

ENGINE GOVERNOR GAIN
ADJUSTMENTS

Engine speed governing is also controlled by the
engine control board. The engine governor has been
set by the factory during final testing of the generator
and should not be adjusted.

If, however, adjustments are necessary, the following
procedure should be followed (Figure 3.2 and Section
3.7):

1. Move DIP switch 8 to the TEST mode (OFF posi-

tion).

2. Set all three potentiometers (pots) fully counter-

clockwise.

3. Under no load condition, increase the GAIN pot

as much as possible without causing instability.

4. Apply 1/4, 1/2, 3/4 and full load to the unit.

Decrease the GAIN pot if there is instability at any
load point.

5. Under full load condition, increase the stability

pot until the unit returns to 60 Hertz (or 50 Hertz
in 50 Hertz applications).

Figure 3.2 — Control Board Dip Switch Location

Section 3 - Operation

Liquid-cooled 15, 20 and 25 kW Generators

Condition

System

Low

Low

High

Over

Over

Switch Position

Ready (Green)

Bat (Red)

Oil (Red)

Temp (Red)

Speed (Red)

Crank (Red)

Manual

Auto

Off

Generator Switch is

OFF

X

OFF

OFF

OFF

OFF

O

in the OFF Mode.

System Ready for

ON

X

OFF

OFF

OFF

OFF

O

Automatic Start

Generator Switch is

OFF

X

OFF

OFF

OFF

OFF

O

in the MANUAL Mode

Weekly Exerciser

X

Flashing

Flashing

Flashing

Flashing

Flashing

O

O

O

is not set

(-----------------------------------1 sec rate---------------------------------------)

Battery Voltage <12.2V

X

ON

O

O

O

for >1 minute

(Non-latching)

Battery Voltage <6V

OFF

ON

O

O

Unit Shutdown due

OFF

X

ON

O

O

to Low Oil Pressure

Unit Shutdown due to
High Coolant Temperature

OFF

X

ON

O

O

or Low Coolant Level

Unit Shutdown due

OFF

X

ON

O

O

to Engine Overspeed

Unit Failed to Start

OFF

X

ON

O

O

during it’s Crank Cycle

Utility Voltage is

Flashing

X

O

O

<45% of Nominal

1 sec rate

Engine Speed Signal Fault

OFF

X

Flashing

O

O

Control Board is

OFF

X

The five RED LED’s will turn on one at a time

O

O

O

in GTS Mode

X = indicates that the LED can be ON or OFF depending on the operating conditions.

Advertising