OPERATING DATA

KW RATING (LP/NG)

130

ENGINE SIZE

6.8 Liter V-10

GENERATOR OUTPUT VOLTAGE/KW - 60Hz

LP

AMP

NG

AMP

CB Size

120/240V, 1-phase, 1.0 pf
120/208V, 3-phase, 0.8 pf
120/240V, 3-phase, 0.8 pf
277/480V, 3-phase, 0.8 pf

130
130
130
130

542
451
391
195

117
122
122
122

488
423
367
183

600
500
450
225

GENERATOR LOCKED ROTOR KVA
AVAILABLE @ VOLTAGE DIP OF 35%

Single phase or 208-240 3-phase
480V 3-phase

270
320

ENGINE FUEL CONSUMPTION

(Natural Gas) (Propane)

Exercise cycle
25% of rated load
50% of rated load
75% of rated load
100% of rated load

For Btu content, multiply ft

3

/hr x 2520 (LP) or ft

3

/hr x 1000 (NG)

Natural Gas

(ft

3

/hr.)

135
482
927

1292
1786

Propane

(gal/hr.)

(

ft

3

/hr.)

1.4

54.5

5.3

193

10.3

373

14.3

520

19.8

719

ENGINE COOLING

Air flow

(inlet air including alternator and combustion air)

ft

3

/min.

System coolant capacity

US gal.

Heat rejection to coolant

BTU/hr.

Max. operating air temp. on radiator

°C (°F)

Max. ambient temperature

°C (°F)

6,450

4.5

496,000

60 (150)
50 (140)

COMBUSTION AIR REQUIREMENTS

Flow at rated power 60 Hz

cfm

336

SOUND EMISSIONS IN DBA

Exercising at 7 meters
Normal operation at 7 meters

65
75

EXHAUST

Exhaust flow at rated output 60 Hz

cfm

Exhaust temp. at muffler outlet

ºC (

°F)

1,119

521 (970)

ENGINE PARAMETERS

Rated synchronous RPM

60 Hz

2970

POWER ADJUSTMENT FOR AMBIENT CONDITIONS

Temperature Deration

3% for every 10 °C above - °C

1.65% for every 10 °F above - °F

Altitude Deration

1% for every 100 m above - m

3% for every 1000 ft. above - ft.

25
77

183
600

RATING: All three phases units are rated at 0.8 power factor. All single phase units are rated at 1.0 power factor. STANDBY RATING: Standby ratings apply to installations served by a
reliable utility source. The standby rating is applicable to varying loads for the duration of a power outage. There is no overload capability for this rating. Ratings are in accordance with
ISO-3046-1. Design and specifications are subject to change without notice.
kW rating is based on LPG Fuel and may derate with natural gas.

Generac

®