Interconnections, Qt130 – Generac Liquid-Cooled Engine Generator Sets Model QT130 (Bisque) User Manual

Page 4

Advertising
background image

INTERCONNECTIONS

NEXUS™ CONTROL FEATURES

2-Line Plain Text LCD Display

Simple user interface for ease of operation.

Mode Switch

-Auto

Automatic Start on Utility failure. 7 day exerciser.

-Off

Stops unit. Power is removed. Control and charger still operate.

-Manual/Test (start)

Start with starter control, unit stays on. If utility fails, transfer to load takes place.

Programmable start delay between 10-30 seconds

Standard

Engine Start Sequence

Cyclic cranking: 16 sec. on, 7 rest (90 sec. maximum duration).

Engine Warm-up

5 seconds

Engine Cool-Down

1 minute

Starter Lock-out

Starter cannot re-engage until 5 sec. after engine has stopped.

Smart Battery Charger

Standard

Automatic Voltage Regulation with Over and Under Voltage Protection

Standard

Automatic Low Oil Pressure Shutdown

Standard

Overspeed Shutdown

Standard, 72Hz

High Temperature Shutdown

Standard

Overcrank Protection

Standard

Safety Fused

Standard

Failure to Transfer Protection

Standard

Low Battery Protection

Standard

50 Event Run Log

Standard

Future Set Capable Exerciser

Standard

Incorrect Wiring Protection

Standard

Internal Fault Protection

Standard

Common External Fault Capability

Standard

Governor Failure Protection

Standard

QT130

*Single and three phase connections may vary, refer to the owner’s manual for specific connection information.

CIRCUIT BREAKER WIRE AND CONDUIT SIZE

kW

VOLTS

CB AMPS

LUG SIZE

130

240 1 Ø

600

(3) 2/0 to 400 mcm

130

240 3 Ø

450

(3) 2/0 to 400 mcm

130

208 3 Ø

500

(3) 2/0 to 400 mcm

130

480 3 Ø

225

(1) 600 mcm or (2) 1/0 to 250 mcm

Advertising