Installation instructions, Site requirements, Gas supply – Stovax PR0696 User Manual

Page 11: Ventilation

Advertising
background image

11

INSTAllATION INSTRUCTIONS

SITE REQUIREMENTS

2

AR0184

A

B

D

C

E

50mm (2")

Flue Type

Dimension

Brick Built

Class 1

Pre Fab Metal

Box

Pre Cast

from 1986

A

410

407

305

B

560

560

560

C

250

200

215

D

300

300

300

E

150

150

150

2.4 Ensure that no naked flame or incandescent part of the fire

bed projects beyond the vertical plane of the fireplace

opening.

2.5 The appliance must not be installed in any room that

contains a bath or shower.

2.6 Ensure clearances to combustible materials - see diagram 3

3

AR0707

3. GAS SUPPlY

3.1 Before installation, ensure that the local distribution

conditions (identification of gas and pressure) and

the adjustment of the appliance are compatible.

3.2 Ensure that the gas supply is capable of delivering the

required amount of gas, and is in accordance with the rules

in force.

3.3 This appliance is supplied complete with a factory fitted

isolation device incorporated into the inlet connection, no

further isolation device is therefore required.

4. vENTIlATION

It is important to ensure that any national ventilation

requirements are taken into account during the

installation of this appliance.

4.1 This appliance has a nominal input not exceeding 7.0kw

and therefore does not normally require ant additional

permanent ventilation.

If, however, spillage is detected when commissioning the

appliance, there may be insufficient natural ventilation and

additional ventilation may be required.

For ventilation requirements in the Republic of Ireland, it

will be necessary to refer to the relevant rules in force.

AIR vENTS MUST NOT BE RESTRICTED.