277

The action keys specify the instance number for an object to perform an action on.
The following action keys are possible:

Action Key

Setpoint
Supported

Meaning

0

-

No action

1000-1004

STD HS

Clear digital input counter 0-3 (Status input counter 1-4), 4=ALL

1100-1102

STD HS

Operate Relay #1 to 3

1C00-1C04

STD HS

same as 1000-1004

A400-A407

STD HS

Waveform Capture channels #1 to 8

A500

STD HS

Waveform Recorder

Action keys marked with STD are supported by Standard Setpoints (1–11), action
keys marked with HS are supported by High Speed Setpoints (1–6).