PMCS Interface Toolkit

{ set the bus status for the incoming feeds to
the dependent bus below in the

distribution hierarchy. The IF_THEN

statements in this section traverse the
hierarchy from top to bottom, left to right,
and then bottom to top, right to left.}
bus6 = 0;
bus7 = 0;

{ two main feeds }
IF (bus1

AND brk1_s) THEN

bus3 = 1;

ENDIF;
IF (bus2

AND brk2_s) THEN

bus4 = 1;

ENDIF;

{ left to right across tie breaker }
IF (bus3

AND brk3_s) THEN

bus4 = 1;

ENDIF;
IF (bus4

AND brk4_s) THEN

bus5 = 1;

ENDIF;

{ two outgoing feeders }
IF (bus3

AND brk5_s) THEN

bus6 = 1;

ENDIF;
IF (bus5

AND brk6_s) THEN

bus7 = 1;

ENDIF;

{ back feed from two outgoing feeds }
IF (bus7

AND brk6_s) THEN

bus5 = 1;

ENDIF;
IF (bus6

AND brk5_s) THEN

bus3 = 1;

ENDIF;

{ right to left across tie breaker }
IF (bus5

AND brk4_s) THEN

bus4 = 1;

ENDIF;
IF (bus4

AND brk3_s) THEN

bus3 = 1;

ENDIF;

{ two incoming feeds }
IF (bus5 AND brk2_s) THEN

bus2 = 1;

ENDIF;
IF (bus3

AND brk1_s) THEN

bus1 = 1;

ENDIF;