GE 90-30 PLC User Manual

Page 83

Advertising
background image

4

4-4

TCP/IP Ethernet Communications User’s Manual – August 1997

GFK-1084B

Table 4-1. PLC Fault Table Descriptions (Continued)

ББББББББББББ

ББББББББББББ

PLC Fault

БББББББББББББББ

БББББББББББББББ

User Action

ББББББББББББ

ББББББББББББ

ББББББББББББ

LAN I/F can’t init - check parms; running
soft Sw utl

БББББББББББББББ

БББББББББББББББ

БББББББББББББББ

Internal system error. User Action: If problem
persists, contact GE Fanuc Automation.

ББББББББББББ

ББББББББББББ

LAN I/F capacity exceeded; discarded re-
quest

БББББББББББББББ

БББББББББББББББ

Verify that connection limits are not being exceeded.

ББББББББББББ

ББББББББББББ

ББББББББББББ

LAN interface hardware failure; switched
off network

БББББББББББББББ

БББББББББББББББ

БББББББББББББББ

User Action: Replace Ethernet Interface.

ББББББББББББ

ББББББББББББ

ББББББББББББ

ББББББББББББ

LAN network problem exists; perfor-
mance degraded

БББББББББББББББ

БББББББББББББББ

БББББББББББББББ

БББББББББББББББ

Excessive backlog of transmission requests due to
excessive traffic on the network. For a sustained pe-
riod the MAC was unable to send frames as quickly
as requested. User Action: If problem persists, con-
tact GE Fanuc Automation.

ББББББББББББ

ББББББББББББ

ББББББББББББ

ББББББББББББ

ББББББББББББ

LAN severe network problem; attempting
recovery

БББББББББББББББ

БББББББББББББББ

БББББББББББББББ

БББББББББББББББ

БББББББББББББББ

External condition prevented transmission of frame
in specified timeframe. Could be busy network or
network problem. User Action: Check transceiver to
make sure it is securely attached to the network.
Check for unterminated trunk cable.

ББББББББББББ

ББББББББББББ

LAN system-software fault; aborted
connection resuming

БББББББББББББББ

БББББББББББББББ

Internal system error. User Action: If problem
persists, contact GE Fanuc Automation.

ББББББББББББ

ББББББББББББ

ББББББББББББ

LAN system-software fault; restarted LAN
I/F

БББББББББББББББ

БББББББББББББББ

БББББББББББББББ

Internal system error. User Action: If problem
persists, contact GE Fanuc Automation.

ББББББББББББ

ББББББББББББ

LAN system-software fault; resuming

БББББББББББББББ

БББББББББББББББ

Internal system error. User Action: If problem
persists, contact GE Fanuc Automation.

ББББББББББББ

ББББББББББББ

ББББББББББББ

ББББББББББББ

LAN transceiver fault; OFF network until
fixed

БББББББББББББББ

БББББББББББББББ

БББББББББББББББ

БББББББББББББББ

Transceiver or transceiver cable failed or became dis-
connected. User Action: Reattach the cable or re-
place the transceiver cable. Check SQE test switch if
present on transceiver.

ББББББББББББ

ББББББББББББ

ББББББББББББ

Local request to send was rejected; dis-
carded request

БББББББББББББББ

БББББББББББББББ

БББББББББББББББ

Internal error. Check that the Ethernet Interface is
online. User Action: If problem persists, contact GE
Fanuc Automation.

ББББББББББББ

ББББББББББББ

ББББББББББББ

ББББББББББББ

Memory backup fault; may lose config/log
on restart

БББББББББББББББ

БББББББББББББББ

БББББББББББББББ

БББББББББББББББ

Internal error accessing FLASH device.
User Action: If problem persists, contact GE Fanuc
Automation. Replace Ethernet Interface.

ББББББББББББ

ББББББББББББ

Module software corrupted; requesting
reload

БББББББББББББББ

БББББББББББББББ

Catastrophic internal system error. Contact GE Fa-
nuc Automation.

ББББББББББББ

ББББББББББББ

ББББББББББББ

Module state doesn’t permit Comm_Req;
discarded

БББББББББББББББ

БББББББББББББББ

БББББББББББББББ

COMMREQ received when Ethernet Interface can-
not process COMMREQ. User Action: Make sure
Ethernet Interface is configured and online.

ББББББББББББ

ББББББББББББ

ББББББББББББ

ББББББББББББ

Unsupported feature in configuration

БББББББББББББББ

БББББББББББББББ

БББББББББББББББ

БББББББББББББББ

PLC firmware does not support ethernet commu-
nications software. User Action: Check CPU revi-
sion, order upgrade kit for CPU.