Rating definitions - Standby: Applicable for supplying emergency power for the duration of the utility power outage. No overload capability is available for this rating. (All ratings in accordance with BS5514,
ISO3046 and DIN6271). * Maximum wattage and current are subject to and limited by such factors as fuel Btu content, ambient temperature, altitude, engine power and condition, etc. Maximum power
decreases about 3.5 percent for each 1,000 feet above sea level; and also will decrease about 1 percent for each 6° C (10° F) above 16° C (60°F). Sound output ratings from certain points on the generator
subject to change based on installation parameters.

Generator

Model

005882-1, 005870-1 (8 kW)

005883-1, 005871-1,

0060651-1 (10 kW)

005884-1, 005872-1,

006052-1 (14 kW)

Rated Maximum Continuous Power Capacity (LP)

8,000 Watts*

10,000 Watts*

14,000 Watts*

Rated Maximum Continuous Power Capacity (NG)

7,000 Watts*

9,000 Watts*

13,000 Watts*

Rated Voltage

240

240

240

Rated Maximum Continuous Load Current – 240 Volts

33.3 LP/29.2 NG

41.6 LP/37.5 NG

58.3 LP/54.2 NG

Total Harmonic Distortion

Less than 5%

Less than 5%

Less than 5%

Main Line Circuit Breaker

35 Amp

45 Amp

60 Amp

Phase

1

1

1

Number of Rotor Poles

2

2

2

Rated AC Frequency

60Hz

60Hz

60Hz

Power Factor

1

1

1

Battery Requirement (not included)

Group 26R 12 Volts and 525

Cold-cranking Amperes Minimum

Group 26R 12 Volts and 525

Cold-cranking Amperes Minimum

Group 26R 12 Volts and 525

Cold-cranking Amperes Minimum

Unit Weight (Pounds/Kilos)

340/154.2

387/175.4

439/199.1

Dimensions (L x W x H) Inches/mm

48 x 25 x 29 (1218 x 638 x 732)

Sound output in dB(A) at 23 ft. with generator operating at normal load

62

63

66

Engine

Type of Engine

GENERAC OHVI

GENERAC OHVI V-TWIN

GENERAC OHVI V-TWIN

Number of Cylinders

1

2

2

Displacement

410cc

530cc

992cc

Cylinder Block

Aluminum w/Cast Iron Sleeve

Aluminum w/Cast Iron Sleeve

Aluminum w/Cast Iron Sleeve

Valve Arrangement

Overhead Valve

Overhead Valve

Overhead Valve

Ignition System

Solid-state w/Magneto

Solid-state w/Magneto

Solid-state w/Magneto

Governor System

Electronic

Electronic

Electronic

Compression Ratio

9.5:1

9.5:1

9.5:1

Starter

12 Vdc

12 Vdc

12 Vdc

Oil Capacity Including Filter

Approx. 1.5 Qts./1.4L

Approx. 1.7 Qts./1.6L

Approx. 1.9 Qts./1.8L

Operating RPM

3,600

3,600

3,600

Fuel Consumption
Natural Gas

ft3/hr.

1/2 Load

Full Load

Liquid Propane

ft3/hr (gal/hr) [Liter/hr]

1/2 Load

Full Load

77

139

34 (0.94) [3.56]
62 (1.68) [6.36]

102
156

46 (1.25) [4.73]
70 (1.93) [7.31]

156
220

58 (1.56) [5.91]
84 (2.30) [8.71]

Required fuel pressure to generator fuel inlet at all load ranges - 5 to 7 inches of water column for natural gas, 10 to 12 inches of water column for LP gas
For Btu content, multiply ft3/hr x 2520 (LP) or ft3/hr x 1000 (NG)

Controls

2-Line Plain Text LCD Display

Simple user interface for ease of operation.

Mode Switch

-Auto

Automatic Start on Utility failure. 7 day exerciser.

-Off

Stops unit. Power is removed. Control and charger still operate.

-Manual/Test (start)

Start with starter control, unit stays on. If utility fails, transfer to load takes place.

Programmable start delay between 10-30 seconds

Standard

Engine Start Sequence

Cyclic cranking: 16 sec. on, 7 rest (90 sec. maximum duration).

Engine Warm-up

5 seconds

Engine Cool-Down

1 minute

Starter Lock-out

Starter cannot re-engage until 5 sec. after engine has stopped.

Smart Battery Charger

Standard

Automatic Voltage Regulation with Over and Under Voltage Protection

Standard

Automatic Low Oil Pressure Shutdown

Standard

Overspeed Shutdown

Standard, 72Hz

High Temperature Shutdown

Standard

Overcrank Protection

Standard

Safety Fused

Standard

Failure to Transfer Protection

Standard

Low Battery Protection

Standard

50 Event Run Log

Standard

Future Set Capable Exerciser

Standard

Incorrect Wiring Protection

Standard

Internal Fault Protection

Standard

Common External Fault Capability

Standard

8/10/14kW specifications

8/10/14kW

®