Features of GE Large Faceplate Wizards

PMCS Interface Toolkit

Power Quality Meter (PQM)

The PQM's large faceplate wizard provides the following animated functions:

Feature

Function

Meter Display

Opens the tabular data window specified during wizard
configuration and sets the view to the Metering tab.

Setpoint button

Opens the tabular data window specified during wizard
configuration and sets the view to the Setpoints tab.

Reset button

Opens the tabular data window specified during wizard
configuration and sets the view to the Metering tab, which offers a
button to issue a RESET command to the device.

Actual button

Pressing the ACTUAL button rotates through the three Main
Actual Value pages on the device: A1 Metering, A2 Status, and A3
Product Info. If the ACTUAL button is pressed while the display
shows a subgroup or a line, the display will jump back to the Page
header.

Message
Up/Down buttons

Scrolls forward/backward through the subgroups for the currently
selected page.

Message
Right/Left
buttons

Scrolls through individual lines for each subgroup within a page.
For most lines, an actual value and units from the device are
displayed.

Panel Display
Lights

Display animation that shows the status of the PQM relay.

Table 8. PQM Faceplate animated functions.

NOTE: The PQM Large Faceplate Wizard cannot display values greater than 2 to
the 31

st

power. Therefore, numbers greater than 2

31

(unscaled) for Energy and

Apparent Energy may appear negative. The values affected are kWh, kvarh, kVAh,
Energy Cost and kVA. The Tabular Data Screen wizard show the correct values.