Specifications – Generac 005875-1 User Manual

Page 3

Advertising
background image

®

Rating definitions - Standby: Applicable for supplying emergency power for the duration of the utility power outage. No overload capability is available for this rating. (All ratings in accordance with BS5514,

ISO3046 and DIN6271). * Maximum wattage and current are subject to and limited by such factors as fuel Btu content, ambient temperature, altitude, engine power and condition, etc. Maximum power

decreases about 3.5 percent for each 1,000 feet above sea level. Sound output ratings from certain points on the generator subject to change based on installation parameters.

GENERATOR

Model 005875-1 (20 kW)

Rated Maximum Continuous Power Capacity (LP)

20,000 Watts*

Rated Maximum Continuous Power Capacity (NG)

18,000 Watts*

Rated Voltage

240

Rated Maximum Continuous Load Current – 240 Volts

83.3 LP/75 NG

Total Harmonic Distortion

Less than 5%

Main Line Circuit Breaker

90 Amp

Phase

1

Number of Rotor Poles

2

Rated AC Frequency

60Hz

Power Factor

1

Battery Requirement (not included)

Group 26R 12 Volts and 525 Cold-cranking Amperes Minimum

Unit Weight (Pounds/Kilos)

451/204.6

Dimensions (L x W x H) Inches/mm

48 x 25 x 29 (1218 x 638 x 732)

Sound output in dB(A) at 23 ft. with generator operating at normal load

66

Sound output in dB(A) at 23 ft. with generator in Quiet-Test™ low speed exercise mode

60

ENGINE

Model 005875-1 (20 kW)

Type of Engine

GENERAC OHVI V-TWIN

Number of Cylinders

2

Displacement

999cc

Cylinder Block

Aluminum w/Cast Iron Sleeve

Valve Arrangement

Overhead Valve

Ignition System

Solid-state w/Magneto

Governor System

Electronic

Compression Ratio

9.5:1

Starter

12 Vdc

Oil Capacity Including Filter

Approx. 1.9 Qts./1.8L

Operating RPM

3,600

Fuel Consumption
Natural Gas

cu.ft./hr.

1/2 Load

Full Load

Liquid Propane

ft3/hr (gal/hr) [Liter/hr]

1/2 Load

Full Load

206
294

69 (1.89) [7.15]

106 (2.90) [10.98]

Required fuel pressure to generator fuel inlet at all load ranges - 5 to 7 inches of water column for natural gas, 10 to 12 inches of water column for LP gas
For Btu content, multiply ft

3

/hr x 2520 (LP) or ft

3

/hr x 1000 (NG)

CONTROLS

2-Line Plain Text LCD Display

Simple user interface for ease of operation.

Mode Switch

-Auto

Automatic Start on Utility failure. 7 day exerciser.

-Off

Stops unit. Power is removed. Control and charger still operate.

-Manual/Test (start)

Start with starter control, unit stays on. If utility fails, transfer to load takes place.

Programmable start delay between 10-30 seconds

Standard

Engine Start Sequence

Cyclic cranking: 16 sec. on, 7 rest (90 sec. maximum duration).

Engine Warm-up

5 seconds

Engine Cool-Down

1 minute

Starter Lock-out

Starter cannot re-engage until 5 sec. after engine has stopped.

Smart Battery Charger

Standard

Automatic Voltage Regulation with Over and Under Voltage Protection

Standard

Automatic Low Oil Pressure Shutdown

Standard

Overspeed Shutdown

Standard, 72Hz

High Temperature Shutdown

Standard

Overcrank Protection

Standard

Safety Fused

Standard

Failure to Transfer Protection

Standard

Low Battery Protection

Standard

50 Event Run Log

Standard

Future Set Capable Exerciser

Standard

Incorrect Wiring Protection

Standard

Internal Fault Protection

Standard

Common External Fault Capability

Standard

SPECIFICATIONS